Note: After you remove a power supply unit (PSU) from the system, it should not be installed again
until five or more seconds has passed. If you apply power sooner, the supply might need to remain
unpowered and out of the system for several minutes to fully discharge internally before you should
try to reinstall it.
4.
If a connector protective cap is installed on your new PSU, remove it before installing the PSU into
your system.
5.
Inspect the new PSU, especially the connector area, for any damage that might have occurred during
shipment.
6.
Slide the new PSU into the empty slot, and push it in until the ejector latch engages and clicks.
Note: While installing the supply, use care to ensure that the supply's connector does not come into
contact with the rear of the chassis.
Platform Maintenance
36