Notes about the Message field
After selecting
Send message
or
Log event
from the
Action type
drop
down menu, a default message will be generated containing the Alarm name
and Input name.
You may replace the message with your own text. The message can be up to
4000 characters long, and can contain special references to insert values
from the system. References always start and end with a
#
-character.
This table lists the possible parameters:
Parameter
Description
#VALx#
Inserts the converted momentary value of input with number x.
#CNTx#
Inserts the counter register value of input number x.
#OUTx#
Inserts the current state (“on” or “off”) of output number x.
#SCHx#
Inserts the current state (“active” or “inactive”) of schedule x.
#STAx#
Inserts the translated input value text from the Text Status box under input settings.
Example of a message using references:
Warehouse temperature is #VAL8# and exhaust fan is #OUTx#
The input/output/schedule number can be looked up by clicking the root
nodes in the resource tree.
Up to four (4) references are allowed in a single message.