Modbus / serial port
The ezeio
™
has one Modbus RTU master port.
The communication default settings are
19200bsp, 8 data bits, No parity
.
The bit rate can be changed from the
Configure
→
System
screen.
Up to 20 Modbus devices (slaves) can be connected to the same Modbus
RTU network, and the network can be up to 1000m (3000ft) long. Note that
the wire length may in some cases be limited by the device specifications
and environmental factors.
RS-485/Modbus RTU port pinout
View into ezeio
™
ModBus port
Pin on
RJ45
Common
nomenclature
EIA/TIA-
485 name
Description
T568A/B
color
4
D1/D+
B/B'
Data 1, V1 Voltage
Blue
5
D0/D-
A/A'
Data 0, V0 Voltage
Blue/white
7
VP
8-25V DC out, max 200mA
Brown/white
8
Common
C/C'
Signal/power supply common
Brown
This pin arrangement conforms to the Modbus specification, 2W-MODBUS
(see
). Pins not listed above are not connected.
Standard Ethernet patch cables are suitable for extending the Modbus
signals. Make sure your cables conform to the T568A/B standard. For long
runs (>100m/300ft) and where interference may be an issue, please consider
using shielded cable and end of line resistors.
We recommend using the color scheme described in the above table.