Inputs – Current sensors
Jumper
setting
Description
0-30mA (suitable for 4-20mA transducers)
An internal 100 Ohm resistor connects the input terminal to Common.
Raw reading is about 10000 at 30mA (3uA per count)
To use 0-30mA (or 4-20mA) sensors, after setting the input jumper as
explained above, connect the current loop sensor between the +DC output
terminal and the input, like this:
The +DC output provides nominally 1V less than the voltage on the DC
input. The standard DC adapter shipped with the ezeio
™
outputs just over
12V. If a higher voltage is required for the current loop sensor, either use a
different adapter for the ezeio
™
, or feed the current loop from an external
source, like this:
The internal current sense resistor in the ezeio
™
is 100
Ω
, so the loop voltage
drop at 20mA will be 2V (
U = R · I
).
Check the data sheet for your current sensor and make sure the voltage
source is at least 2V higher than the minimum voltage for your sensor.