MLC 104 IP Plus Series • Firmware Updates
159
12.
Close or exit Firmware Loader.
13.
Verify that the MLC is connected to the network and is functioning as expected.
Resetting the MLC and Restoring its Configuration
After a firmware update you must reset the unit. Resetting the MLC also removes
configuration information, so replace the configuration of the MLC after resetting.
1.
Perform a ZY reset, which is an absolute system reset
excluding
IP settings (IP
address, subnet mask, gateway IP address, unit name, DHCP settings, port mapping).
This allows you to maintain communication with the MLC.
•
If using DataViewer, Telnet, or HyperTerminal, enter
E
ZY
}
.
•
If using a web browser connection, enter
W ZY
|
.
NOTES:
•
This command is supported by MLCs with firmware of version 1.03 or higher.
•
The ZY reset is different from reset modes 1 through 4. For details about reset
modes available using SIS commands, see
2.
Using Global Configurator, restore (build) the previously saved project to the MLC.