BOILER DISPLAY TABLES
31
Chapter 10
BOILER DISPLAY TABLES
LUMINOUS INDICATORS
Indicators
Description
Explanation
A
It indicates functioning of the fumes
expulsion motor.
It is on/off when the fumes exhaust motor is activated/deactivated.
It fl ashes when the speed control probe (encoder) is disconnected.
B
Indicates the consent for pump
functioning.
It is on/off to indicate functioning consent/dissent for the circulation
pump.
C
Indicates the consent for pump/external
electro-thermal controls functioning.
It is on/off to indicate functioning consent/dissent for the external
electro-thermal pumps/controls.
D
It indicates functioning of the pellet feed
motor.
It is on/off when the pellet feed motor is activated/deactivated.
The indicator switches on intermittently during normal functioning as
the motor works with impulses.
Indicates the presence of an alarm.
It is on in the presence of an alarm and is accompanied by the relative
signal in the display, which identifi es the cause. To reset the alarm, just
hold key 1(esc) down for 3 seconds when the boiler is completely cold.
Not used
Preparation for future applications
Indicates the status of zone 1 thermostat.
The indicator is on/off when the external thermostat has to be satisfi ed/
dissatisfi ed. If to be satisfi ed, i.e. heat request, activate the relative pump/
electro-thermal control for the circulation of water.
The activation of this pump/electro-thermal control takes place also if
the temperature of the water inside the boiler exceeds 87°C (overheating
safety device).
In this case the pump/electro-thermal control stops when the
temperature of the water falls below 85°C.
Indicates the status of zone 2 thermostat.
The indicator is on/off when the external thermostat has to be satisfi ed/
dissatisfi ed. If to be satisfi ed, i.e. heat request, activate the relative pump/
electro-thermal control for the circulation of water.
Indicates the functioning of the lambda
probe.
The indicator is on/off when the lambda probe is activated/deactivated.
Indicates the status of the serial port.
The indicator is on/off when the serial communication with the electronic
board is disabled/enabled.
Indicates deactivation of the ign-plug for
automatic ignition.
It is off /on when the electrode is activated/deactivated.
Not used
Preparation for future applications
Содержание TERMOPELLET TP30
Страница 2: ...2 ...
Страница 4: ...4 ...
Страница 10: ...TECHNICAL FEATURES 10 Chapter 2 figure 2 1 ...