background image

7

ENGLISH

InstallIng Inserts

When installing inserts, access must be prevented to the internal parts of the appliance and it must not be possible to access live parts during 

extraction operations.

Any wiring, for example the power cable or room probe, must be positioned so as not to be damaged during movement of the insert and must 

not come into contact with hot parts. If a cavity made of combustible material is installed, we recommend taking all the safety precautions 

indicated by the installation standards.

VentIlatIOn anD aeratIOn OF InstallatIOn rOOMs

In case of non-airtight heater and/or installation, the ventilation must respect the minimum area indicated below (considering the highest value 
among those provided):

Appliance categories

Reference standard

Percentage of the 

net opening section with respect to the 

appliance fumes outlet section

Minimum net opening value of the 

ventilation duct

Pellet stoves

UNI EN 14785

-

80 cm²

Boilers

UNI EN 303-5

50%

100 cm²

InstallatIOn

general

The flue gas exhaust and hydraulic connections must be carried out by qualified personnel who must issue installation conformity 

documentation compliant with national standards.

The installer must provide the owner or person acting for him, according to the legislation in force, with the declaration of conformity, 

supplied with:

1) the use and maintenance manual of the appliance and of the system components (such as for example, the smoke ducts, chimney, etc.);

2) photocopy or photograph of the chimney plaque;

3) system booklet (where applicable).

The installer must ask to be issued with a receipt stating that the documentation has been provided, and must keep it with a copy of the technical 

documentation relating to the installation.

For installation in a condominium, prior approval from the condominium's administrator must be requested.

Where required, check the exhaust gas emissions after installation. Should a sampling point be installed, it must be airtight.

COMPatIBIlItY 

Do not install in rooms with a fire hazard. It is also forbidden to install it in living areas with the following characteristics:

1.  where there are liquid fuel appliances with continuous or discontinuous operation that draw the combustion air into the room in which they 

are installed.

2.  where there are type B gas appliances intended for heating, with or without domestic hot water production and in adjacent and communicating 

rooms.

3.  where the depression measured in situ between the external and internal environment is greater than 4 Pa.

N.B.: Watertight appliances can also be installed in the cases indicated in points 1, 2 and 3 of this paragraph.

InstallatIOns In BathrOOMs, BeDrOOMs anD stuDIO Flats

Installation in bathrooms, bedrooms and studio flats is only allowed for sealed or closed hearth appliances with ducted combustion air taken 

from the outside.

floor protection

POsItIOnIng anD saFetY DIstanCes 

The support surfaces and/or points must have a suitable capacity to bear the overall weight 
of the appliance, accessories and coverings. If the floor is made of a combustible material, 
we recommend using a non-combustible material to protect the front part from any burnt 
material which might fall during routine cleaning operations. The generator must be level 
to function properly.  The side walls, the rear walls and the floor support surface should be 
made of non-combustible material.

One must also bear in mind all laws and national, 

regional, provincial and town council regulations in force 

in the country in which the appliance has been installed, 

as well as the instructions contained in this manual.

Air inlet

Under any condition, including in the presence of extractor hoods and/or of controlled forced ventilation systems, the pressure difference 

between the generator installation rooms and the outside must always be equal to or less than 4 Pa.

MInIMuM DIstanCes

Installation next to flammable or heat-sensitive materials is permitted 

only if the special 

safety distances specified on the label at the beginning of the manual (pag.2) are 

observed

. If the materials are not flammable, you must keep a side and rear distance of at 

least 100 mm (without the inserts). For products equipped with rear spacers, wall-mounting 
installation is permitted exclusively for the rear side.

PreParatIOns FOr MaIntenanCe

To carry out extraordinary maintenance operations on the product, it may be necessary to move it away from the adjacent walls. This must be 

done by a technician authorised to disconnect the combustion product evacuation ducts and then reconnect them. For heaters connected to the 

hydraulic system, the connection between the system itself and the product must be made in such a way that, when an authorised technician is 

about to carry out extraordinary maintenance operations, it is possible to move the heater at least 1 metre away from the adjacent walls.

Содержание Marilena Plus AD

Страница 1: ...MADE IN ITALY design production MARILENA PLUS AD 004277269 Rev 000 UK pellet stoves USER MANUAL...

Страница 2: ...2 ENGLISH...

Страница 3: ...Enabling disabling the chrono 20 Settings 22 Display 22 stand by 22 OPERATION with additional thermostat optional 22 Additional thermostat 23 Installation of additional thermostat 23 delta t 23 First...

Страница 4: ...well as the instructions contained in this manual The Manufacturer cannot be held responsible for the failure to comply with such precautions After removing the packaging ensure that the content is in...

Страница 5: ...ply cable so that it does not come into contact with hot parts ofthe appliance The power supply plug must be accessible after installation Do not close or reducethe dimensions ofthe airingvents in the...

Страница 6: ...uid is used the latter could penetrate inside the crackles highlighting them SINCE THE PRODUCT CAN TURN ON AUTOMATICALLY THANKS TO THE TIMER OR REMOTELY USING THE DEDICATED APPLICATIONS IT IS STRICTLY...

Страница 7: ...thoutdomestichotwaterproductionandinadjacentandcommunicating rooms 3 where the depression measured in situ between the external and internal environment is greater than 4 Pa N B Watertight appliances...

Страница 8: ...tion If the exhaust is not inserted in an existing flue a vertical section with a windproof end piece is required UNI 10683 The vertical duct can be inside or outside the building If the smoke duct is...

Страница 9: ...K Combustion air inlet C Combustion chamber access L On Off D Lateral fumes exhaust Fuse E Room air output 230v power supply F Display M Serial input G Upper fumes exhaust Additional thermostat input...

Страница 10: ...allow for the duct motor to be controlled regardless of stove operation At this point simply set the desired temperature on the thermostat the thermostat will command the operation of the second moto...

Страница 11: ...llowing CLOSE HOPPER DOOR This message indicates that you have 60 seconds to close the hatch door and pellet lid After the 60 seconds during the ignition phase the stove will go to DEPR ALARM mode whi...

Страница 12: ...OOR QUALITY PELLETS OR ANY OTHER MATERIAL WILL COMPROMISE STOVE FUNCTIONS VOIDING THE WARRANTY AND RELEASING THE MANUFACTURER OF LIABILITY Pellet hopper pressurised closure During stove operation the...

Страница 13: ...On off stove hold for 3 seconds 9 Degrees Celsius Fahrenheit 4 Set power 10 Press the button once to enable or disable the chrono 5 Set switch off delay The button allows to set the switch off delay F...

Страница 14: ...gnal receiver Handle the remote control with care When it is not being used place it on the special base supplied The remote control must not be left in a place where it is exposed to direct sunlight...

Страница 15: ...bled On the function is enabled Indicates the stove modulation On the stove is operating at the set power Flashing the power at which the stove is operating is not the set power the stove is modulatin...

Страница 16: ...t is recommended to Ventilate the room well If present remove any majolica parts from the top of the product Activate the product at the maximum power and temperature Avoid remaining in the room for a...

Страница 17: ...eturn to the previous menus to the initial state Language This menu allows you to set the preferred language The available languages are Italian English German French Spanish Portuguese Controls proce...

Страница 18: ...e the set temperature has been reached the stove automatically reduces the power ensuring optimal comfort and reducing the consumption of pellets this process is called modulation LOW TA hot If the Se...

Страница 19: ...CREASE RANGE SECOND INCREASE RANGE IF THE FIRST IS NOT ENOUGH THIRD INCREASE RANGE IF THE FIRST TWO ARE NOT ENOUGH Controls procedure Press 6 Press key 3 until easy setup appears and confirm by pressi...

Страница 20: ...g3 1 5 Set power PRG3 prg4 Start prg4 OFF 00 00 Ignition time PRG4 Stop prg4 OFF 00 00 Switch off time PRG4 Monday Sunday On off Enable disable the days of PRG4 Set prg4 LOW TA 07 37 C HOT Set thermos...

Страница 21: ...23 00 08 00 16 30 t 22 18 2 1 21 ENGLISH Time slot 1 start 02 00 stop 23 00 power 3 set thermostat 22 C Time slot 2 start 08 00 stop 16 30 power 1 set thermostat 18 C stove operation Time slot Set po...

Страница 22: ...exceeds the value of the Set Thermostat DELTA T OFF then the stove will switch off after a preset delay displaying STAND BY When the room temperature is lower than the Set Thermostat DELTA T and afte...

Страница 23: ...pears and confirm by pressing 6 Use keys 4 5 to enable ON disable OFF Press 1 several times to confirm and exit the menu J FOR CORRECT OPERATION SET THE SET ROOM THERMOSTAT TO LOW TA Additional thermo...

Страница 24: ...e to comply with these instructions may damage the surfaces of the generator and result in the invalidation of the warranty Cleaning the ceramic glass Never use abrasive or chemically aggressive deter...

Страница 25: ...ied Put the burn pot back in place and push it towards the back wall Put the pellet slide assembly back in place above the burn pot Make sure that the burn pot and pellet slide have been positioned co...

Страница 26: ...26 ENGLISH Cleaning the combustion chamber deflector Remove the deflector and eliminate the ash that has deposited at the top of the deflector...

Страница 27: ...o clean and remove the burn pot it is necessary to remove the pellet slide assembly B by lifting it To put it back in place perform the same operation in reverse order After repositioning it make sure...

Страница 28: ...rranty SEALS pellet hopper lid DOOR ASH DRAWER AND BURN POT The seals ensure that the stove is airtight and they guarantee the proper operation of the same They must be regularly checked if they are f...

Страница 29: ...ed points B Seals pallet hopper inspections ash drawer and door replace and apply silicone where required C Combustion chamber exchanger total cleaning including cleaning the glow plug duct D Hopper e...

Страница 30: ...ed points B Seals pallet hopper inspections ash drawer and door replace and apply silicone where required C Combustion chamber exchanger total cleaning including cleaning the glow plug duct D Hopper e...

Страница 31: ...by pressing key 1 for 3 seconds Fumes motor fault Fumes motor failure Contact the service centre Fumes probe Fumes probe fault Contact the service centre Hot fumes High exhaust temperature Check pell...

Страница 32: ...bility to use the product and wrong maintenance by the consumer with respect to what is reported and recommended by the instructions manual of the product which is part of the sales contract this guar...

Страница 33: ...aults in the electrical insulation This can cause electric shocks Installations not complying with the regulations in force as well as incorrect use and failure to comply with the maintenance schedule...

Страница 34: ...34 ENGLISH...

Страница 35: ...35 ENGLISH...

Страница 36: ...extraflame it www lanordica extraflame com TO FIND THE SERVICE CENTRE NEAREST TO YOU CONTACT YOUR DEALER OR CONSULT THE SITE WWW LANORDICA EXTRAFLAME COM The manufacturer reserves the right to vary th...

Отзывы: