3 - 5%

Max 3 mt

8

ENGLISH

ExAMPlEs of coRREcT connEcTion To ThE chiMnEy

In the presence of type B gas appliances with intermittent operation not intended for heating, they must have their own aeration and/or 

ventilation opening. 

The air inlets must meet the following requirements:

 

Š

they must be protected with grids, metal mesh, etc., but without reducing the net useful section;

 

Š

they must be made so as to make the maintenance operations possible;

 

Š

positioned so that they cannot be obstructed;

The clean and non-contaminated air flow can also be obtained from a room adjacent to that of installation (indirect aeration and 

ventilation), as long as the flow takes place freely through permanent openings communicating with the outside.

The adjacent room cannot be used as a garage, or to store combustible material or for any other activity with a fire hazard, bathroom, 

bedroom or common room of the building.

Flue gas eXhaust

The heat generator works in depression and is equipped with an outlet fan for flue gas extraction. There must be a single exhaust system for 

the generator. Using a flue that is shared with other devices is not allowed.

The components of the flue gas exhaust system must be chosen in relation to the type of appliance to be installed in compliance with:

 

Š

UNI/ TS 11278 in the event of metal chimneys, with particular attention to that stated in the specification; 

 

Š

UNI EN 13063-1 and UNI EN 13063-2, UNI EN 1457, UNI EN 1806 in the event of non-metallic chimneys.

 

Š

The length of the horizontal section must be minimal and, in any case, no longer than 3 metres, with a minimum upward slope of 3%

 

Š

There must not be more than 4 direction changes including the one due to the use of the "T" element.

 

Š

A “T” fitting with a condensation collection cap must be provided at the base of the vertical section.

 

Š

If the exhaust is not inserted in an existing flue, a vertical section with a windproof end piece is required (UNI 10683).

 

Š

The vertical duct can be inside or outside the building. If the smoke duct is inserted in an existing flue, it must be certified for solid fuel.

 

Š

If the smoke duct is outside the building, it must always be insulated.

 

Š

The smoke ducts must have at least one airtight inlet for flue gas sampling.

 

Š

All the sections of the flue gas duct must be accessible to inspection.

 

Š

Inspection openings must be provided for cleaning.

 

Š

If the generator has a fume temperature lower than  160°C+ ambient temperature caused by the high yield (contact technicians) it 

MUST be resistant to humidity.

 

Š

A flue system that does not respect the previous points or, in general, that does not comply with the regulations, may cause condensation 

phenomena inside it.

ChIMneY CaP

The chimney caps must meet the following requirements:

 

Š

they must have a useful outlet section no less than double that of the chimney/ducted system on which it is installed;

 

Š

they must be adapted in order to prevent the penetration of rain and snow in the chimney/ducted system;

 

Š

they must be built so that, in the event of winds coming from all directions and from any angle, the expulsion of combustion products 

is in any case ensured;

Protection from rain 

and wind

Condensation-proof 

"T" fitting with 

inspection plug 

Insulated flue

Insulated "T" 

fitting with 

inspection plug

Protection from rain and wind

"T" fitting with 

i n s p e c t i o n 

plug

COnneCtIOn tO the MaIns eleCtrIC suPPlY

The generator is supplied with an electric power cable to be plugged into a 230V 50 Hz socket, possibly with a circuit breaker switch. The 

socket must be easily accessible.

The electrical system must be compliant with standards. The efficiency of the earthing circuit must be checked. Unsuitable earthing of the 

system can cause malfunctioning for which the manufacturer will not be held liable. 

Power supply variations beyond 10% can cause faulty operation of the product.

Содержание Marilena Plus AD

Страница 1: ...MADE IN ITALY design production MARILENA PLUS AD 004277269 Rev 000 UK pellet stoves USER MANUAL...

Страница 2: ...2 ENGLISH...

Страница 3: ...Enabling disabling the chrono 20 Settings 22 Display 22 stand by 22 OPERATION with additional thermostat optional 22 Additional thermostat 23 Installation of additional thermostat 23 delta t 23 First...

Страница 4: ...well as the instructions contained in this manual The Manufacturer cannot be held responsible for the failure to comply with such precautions After removing the packaging ensure that the content is in...

Страница 5: ...ply cable so that it does not come into contact with hot parts ofthe appliance The power supply plug must be accessible after installation Do not close or reducethe dimensions ofthe airingvents in the...

Страница 6: ...uid is used the latter could penetrate inside the crackles highlighting them SINCE THE PRODUCT CAN TURN ON AUTOMATICALLY THANKS TO THE TIMER OR REMOTELY USING THE DEDICATED APPLICATIONS IT IS STRICTLY...

Страница 7: ...thoutdomestichotwaterproductionandinadjacentandcommunicating rooms 3 where the depression measured in situ between the external and internal environment is greater than 4 Pa N B Watertight appliances...

Страница 8: ...tion If the exhaust is not inserted in an existing flue a vertical section with a windproof end piece is required UNI 10683 The vertical duct can be inside or outside the building If the smoke duct is...

Страница 9: ...K Combustion air inlet C Combustion chamber access L On Off D Lateral fumes exhaust Fuse E Room air output 230v power supply F Display M Serial input G Upper fumes exhaust Additional thermostat input...

Страница 10: ...allow for the duct motor to be controlled regardless of stove operation At this point simply set the desired temperature on the thermostat the thermostat will command the operation of the second moto...

Страница 11: ...llowing CLOSE HOPPER DOOR This message indicates that you have 60 seconds to close the hatch door and pellet lid After the 60 seconds during the ignition phase the stove will go to DEPR ALARM mode whi...

Страница 12: ...OOR QUALITY PELLETS OR ANY OTHER MATERIAL WILL COMPROMISE STOVE FUNCTIONS VOIDING THE WARRANTY AND RELEASING THE MANUFACTURER OF LIABILITY Pellet hopper pressurised closure During stove operation the...

Страница 13: ...On off stove hold for 3 seconds 9 Degrees Celsius Fahrenheit 4 Set power 10 Press the button once to enable or disable the chrono 5 Set switch off delay The button allows to set the switch off delay F...

Страница 14: ...gnal receiver Handle the remote control with care When it is not being used place it on the special base supplied The remote control must not be left in a place where it is exposed to direct sunlight...

Страница 15: ...bled On the function is enabled Indicates the stove modulation On the stove is operating at the set power Flashing the power at which the stove is operating is not the set power the stove is modulatin...

Страница 16: ...t is recommended to Ventilate the room well If present remove any majolica parts from the top of the product Activate the product at the maximum power and temperature Avoid remaining in the room for a...

Страница 17: ...eturn to the previous menus to the initial state Language This menu allows you to set the preferred language The available languages are Italian English German French Spanish Portuguese Controls proce...

Страница 18: ...e the set temperature has been reached the stove automatically reduces the power ensuring optimal comfort and reducing the consumption of pellets this process is called modulation LOW TA hot If the Se...

Страница 19: ...CREASE RANGE SECOND INCREASE RANGE IF THE FIRST IS NOT ENOUGH THIRD INCREASE RANGE IF THE FIRST TWO ARE NOT ENOUGH Controls procedure Press 6 Press key 3 until easy setup appears and confirm by pressi...

Страница 20: ...g3 1 5 Set power PRG3 prg4 Start prg4 OFF 00 00 Ignition time PRG4 Stop prg4 OFF 00 00 Switch off time PRG4 Monday Sunday On off Enable disable the days of PRG4 Set prg4 LOW TA 07 37 C HOT Set thermos...

Страница 21: ...23 00 08 00 16 30 t 22 18 2 1 21 ENGLISH Time slot 1 start 02 00 stop 23 00 power 3 set thermostat 22 C Time slot 2 start 08 00 stop 16 30 power 1 set thermostat 18 C stove operation Time slot Set po...

Страница 22: ...exceeds the value of the Set Thermostat DELTA T OFF then the stove will switch off after a preset delay displaying STAND BY When the room temperature is lower than the Set Thermostat DELTA T and afte...

Страница 23: ...pears and confirm by pressing 6 Use keys 4 5 to enable ON disable OFF Press 1 several times to confirm and exit the menu J FOR CORRECT OPERATION SET THE SET ROOM THERMOSTAT TO LOW TA Additional thermo...

Страница 24: ...e to comply with these instructions may damage the surfaces of the generator and result in the invalidation of the warranty Cleaning the ceramic glass Never use abrasive or chemically aggressive deter...

Страница 25: ...ied Put the burn pot back in place and push it towards the back wall Put the pellet slide assembly back in place above the burn pot Make sure that the burn pot and pellet slide have been positioned co...

Страница 26: ...26 ENGLISH Cleaning the combustion chamber deflector Remove the deflector and eliminate the ash that has deposited at the top of the deflector...

Страница 27: ...o clean and remove the burn pot it is necessary to remove the pellet slide assembly B by lifting it To put it back in place perform the same operation in reverse order After repositioning it make sure...

Страница 28: ...rranty SEALS pellet hopper lid DOOR ASH DRAWER AND BURN POT The seals ensure that the stove is airtight and they guarantee the proper operation of the same They must be regularly checked if they are f...

Страница 29: ...ed points B Seals pallet hopper inspections ash drawer and door replace and apply silicone where required C Combustion chamber exchanger total cleaning including cleaning the glow plug duct D Hopper e...

Страница 30: ...ed points B Seals pallet hopper inspections ash drawer and door replace and apply silicone where required C Combustion chamber exchanger total cleaning including cleaning the glow plug duct D Hopper e...

Страница 31: ...by pressing key 1 for 3 seconds Fumes motor fault Fumes motor failure Contact the service centre Fumes probe Fumes probe fault Contact the service centre Hot fumes High exhaust temperature Check pell...

Страница 32: ...bility to use the product and wrong maintenance by the consumer with respect to what is reported and recommended by the instructions manual of the product which is part of the sales contract this guar...

Страница 33: ...aults in the electrical insulation This can cause electric shocks Installations not complying with the regulations in force as well as incorrect use and failure to comply with the maintenance schedule...

Страница 34: ...34 ENGLISH...

Страница 35: ...35 ENGLISH...

Страница 36: ...extraflame it www lanordica extraflame com TO FIND THE SERVICE CENTRE NEAREST TO YOU CONTACT YOUR DEALER OR CONSULT THE SITE WWW LANORDICA EXTRAFLAME COM The manufacturer reserves the right to vary th...

Отзывы: