WARNING: 

Always test on a  known  good circuit before 

use. 

WARNING: 

Refer all indicated problems to  a qualified 

electrician. 

Locating  a  Circuit  Breaker or  Fuse 

The transmitter injects a signal onto  the circuit  which can  be 
detected by the receiver.  The  receiver  will beep when the 
signal  is detected.  The  sensitivity adjustment allows  for tracing 
and pinpointing  the exact circuit breaker or fuse  protecting the 
selected circuit. 

1. 

Plug the Transmitter 

Receptacle Tester into  a  powered 

outlet.  The two  green  LED's  should  illuminate. 

2. 

Rotate the  Receiver's  Sensitivity  adjustment from the 

OFF 

position  to  the 

HI 

position.  The red  LED should turn 

on.  If  the  LED does not turn  on,  replace  the  battery. 

3. 

Test the operation  of  the  Receiver  by  placing it  in  close 

proximity  to  the transmitter.  The receiver should  beep 
and the  LED should flash. 

4. 

At the  breaker  panel,  set the sensitivity  to  the 

HI 

position 

and  hold  the receiver as indicated by the "UP - DOWN" 
label. 

5. 

Move  the  receiver along the  row  of  breakers until the 
selected  circuit is identified  by  the  beep  and  flashing  light. 

6. 

Reduce  the sensitivity as needed to pinpoint the  exact 
circuit breaker controlling the  circuit. 

Receptacle  Wiring  Test 

CORRECT  WIRING 

.0. 

GFCI TESTING 

HOT  ON NEUTRAL WITH  HOT  OPEN 

HOT AND  GROUND  REVERSED 

HOT AND  NEUTRAL  REVERSED 

OPEN  HOT 

000 

OPEN  NEUTRAL 

00. 

OPEN  GROUND 

OFF 

• 

ON 

1. 

Plug the Transmitter 

Receptacle tester into the outlet. 

2. 

The  three  LED's  will  indicate  circuit  condition.  The 

diagram  lists  all  of  the conditions  that  the 

CB10 

can 

detect.  The  LED's  in this diagram repr&sent  the  view 
from the 

GFCI 

button side  of  the transmitter.  When 

viewing  the  other  side of  the transmitter the  LED's  will  be 
a mirror image of those shown here. 

3. 

The  tester will not indicate the quality of the ground 

connection,  2 hot wires  in  a  circuit,  a  combination of 
defects,  or  reversal  of  ground and neutral conductors. 

Receptacle  GFCI  Test 

1. 

Before using  the  tester,  press the TEST button  on  the 

installed 

GFCI 

receptacle,  the 

GFCI 

should trip.  If  it does 

not  trip,  do not use the circuit and call a  qualified 
electrician.  If it does trip,  press  the  RESET  button  on  the 
receptacle. 

2. 

Plug the Transmitter 

Receptacle  tester  into the outlet. 

Verify  that the wiring  is correct  as described above. 

3. 

Press and  hold the  test button  on  the  tester for at least 8 

seconds,  the indicator lights  on  the  tester will shut off 
when  the 

GFCI 

trips. 

4. 

If  the  circuit  does not trip,  either  the 

GFCI 

is  operable  but 

the wiring is incorrect,  or  the wiring  is  correct and the 

GFCI 

is  inoperable. 

Replacing  the  Battery 

1. 

When  the battery drops below the  operating voltage  the 
receiver's  LED will not light.  The  battery  should be 
replaced 

2.  Remove receiver battery  cover by  removing the screw 

using a  Philips  head screwdriver.  (The Transmitter  is  line 
powered.) 

3.  Install 

volt battery observing the correct polarity. 

4.  Re-install battery cover 

5. 

Dispose  of  the  old  battery  properly. 

B� 

Support  line  (781) 890-7440 

Technical support:  Extension 200;  E ·mail:  [email protected] 

Repair 

Returns:  Extension 210;  E·mail:  [email protected] 

Product specifications subject to  change without  notice 

For  the  latest Version  of  this  User  Guide,  Software  updates,  and other 

up·to-the·minute  product information,  visit our  website:  www.extech.com 

Extech  Instruments Corporation,  285  Bear  Hill  Road,  Waltham, 

MA 

02451 

Copyright 

© 2006 

Extech  Instruments Corporation. 

All  rights reserved including  the right  of reproduction in whole or 
in part  in  any  form. 

CB10 

V2.0 

08/06 

www 

. ElectricalPartManuals 

. com

Содержание CB10

Страница 1: ...pprovals UL Listed Warranty 90 to 120V 47 to 63Hz 9V battery receiver 41QF to 104QF 5QC to 402C _4 F to 140 F 20 C to 60 C Max 80 up to 87QF 31QC decreasing linearly to 50 at 104QF 402C 80 7000ft 2000meters maximum 5 90z 167g 8 5 x 2 2 x 1 5 215 x 56 x 38mm UL CE The UL mark does not indicate that this product has been evaluated for the accuracy of its readings EXTECH INSTRUMENTS CORPORA TlON warr...

Страница 2: ... side of the transmitter the LED s will be a mirror image of those shown here 3 The tester will not indicate the quality of the ground connection 2 hot wires in a circuit a combination of defects or reversal of ground and neutral conductors Receptacle GFCI Test 1 Before using the tester press the TEST button on the installed GFCI receptacle the GFCI should trip If it does not trip do not use the c...

Страница 3: ... Utilisation Poids Dimensions Max 80 jusqu a 31 C 87 F decroit lineairement jusqu a 50 a 400C 104 F 80 2000 metres 7000 ft maximum 5 90z 167g 8 5 x 2 2 x 1 5 215 x 56 x 38mm Normes de securite approuvees UL CE Norme de securite UL Le label UL n indique pas que ce produit a ete evalue pour la precision de ses mesures Garantie EXTECH INSTRUMENTS CORPORATION garantil que eel instrument est exempt de ...

Страница 4: ... emetteur les LED seront une image inversee de ceux montres ici 3 Le testeur n indiquera pas la qualite du branchement de masse 2 circuits trafiques dans un circuit une combinaison de defauts ou I inversement des conducteurs de masse et neutres Recipient Test GFCI 1 Avant d utiliser Ie testeur appuyez sur Ie bouton TEST sur Ie recipient GFCI installe il devrait remuer S il ne remue pas n utilisez ...

Страница 5: ...1 C 87 F con disminuci6n linear hasta 50 a 40 C 104 F Humedad almacenamiento 80 Altitud de operacion Peso Dimensiones Aprobacion Inscrito en UL Garantia 7000ft 2000 metros maxima 167g 5 90z 215 x 56 x 38mm 8 5 x 2 2 x 1 5 ULCE La marca UL no indica que este producto ha sido evaluado en cuanto a la precision de sus lecturas EXTECH INSTRUMENTS CORPORA TlON garantiza este instrumento para estar fibre...

Страница 6: ...or no indica la calidad de la conexion a tierra 2 alambres con corriente conectados a un circuito una combinacion de defectos 0 conductores tierra y neutro invertidos Prueba de enchufe leFT 1 Ant s de usar el probador presione el boton TEST en el enchufe ICFT instalado el ICFT debe dispararse Si no 10 hace no use el circuito y lIame a un electricista calificado Si se dispara presione el boton RESE...

Страница 7: ...User s manual located between cardboard packaging Adjustable sensitivity for pinpointing the correct breaker w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 8: ... FIber Optic Meters Water Quality Meters Extech Instruments Corporation www extech com Copyr glltC 20117 21108ExI hInslrumenls CotporaUoo All rightstIIS Ved including tfIe rightollOfXOdu liooin _ IX in rt In anylann aker Finder i I II 7 93950 40010 4 1 nZP4 1111111111111111111111111111111 11TZP4 CB10 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Отзывы: