When the number of readings in String B matches the number of float readings in String A
(the User has completed the first set of cell discharge readings) the DLV40 automatically
increments to String C.
The User can now start recording the
second set
of discharge cell readings in string C. This
process is repeated until the discharge test is completed or all the available Strings (B
through H) have been used.
Next String!
Dischg
0:12:01
+0.000
C:001
000.0
Sum of cell voltages for
the selected string.
(Shows
000.0V
as
no
discharge readings have
been taken).
Discharge Time
(showing
12
minutes
and
01
second into the
test).
Current Test Mode
Selected String (“C”) and
the next reading in the
selected string (“001”).
(
No
readings have been
taken).