5.2 Step 2: Measure String Float Cell Voltages
(i)
Ensure the DLV40 USB cable is
DISCONNECTED
(ii)
Turn the DLV40
ON.
(iii)
If
NOT
in
“Discharge Test”
mode:
A.
If not in Main Menu, press the
“MENU”
button
twice
to enter the Main Menu:
(v)
Use the “
UP”
or “
DOWN”
buttons to scroll to Discharge Test Mode:
(vi)
Press
“ENTER”
to select.
(iv)
Ensure String A (Float Voltages) is selected and
ALL
previous discharge test data has been
deleted.
(v)
Connect voltage measurement probes to DLV40 and measure float cell voltages ensuring
that the cell number of the
next reading
matches with the cell number counter in the
bottom left hand corner of the display.
Dischg
Float
+0.000
A:001
000.0
Current Test Mode
Selected String (“A”)
and the
next reading
in
selected string (“000”).
Sum of cell voltages
for the selected
string.
Discharge Time
*** Main Menu***
MODE : 8 by 256
*** Main Menu***
MODE : DISCHARGE
If any previous discharge test data had been deleted then the DLV40 display should
match that shown below. If not, please erase ALL previous data (see Step 1 above).
The DLV40 USB cable
MUST
be
DISCONNECTED
whenever measuring voltages!