(iii)
To
DELETE
ALL
existing discharge test data:
A. Press the
“MENU”
button
once
to enter the Discharge Menu:
B.
Use the “
UP”
or “
DOWN”
buttons to scroll to Discharge Test Mode:
Dischg
Float
+0.000
A:011
025.4
Discharge Test
String A : 010 Readings
String A
is reserved for
float
voltages – cell voltage(s) BEFORE a load is
attached to the battery.
Strings B through H
are reserved for
discharge test
cell voltages. Cell voltages
AFTER
a load is attached to the battery.
As shown, String A contains
10
readings and hence there is
existing
Discharge
Test data and the DLV40 is not ready to start a
new
discharge test. See below
for instruction on deleting ALL existing discharge test data.
Current Test Mode
Selected String (“A”)
and
next reading
in the
selected string (“11”)
Sum of cell voltages for
the selected string.
Discharge Time
** Discharge Menu**
Print String?
** Discharge Menu **
Delete DC Test ?