13. Routine Maintenance Inspection Record
Page
26
of
28
13. Routine Maintenance Inspection Record
EXHEAT Industrial Ltd
Threxton House
Threxton Road Ind. Est.
Watton, Thetford, Norfolk
IP25 6NG, United Kingdom
Tel: +44 (0) 1953 886 210
Fax: +44 (0) 1953 883 853
www.exheat-industrial.com
ROUTINE MAINTENANCE
INSPECTION RECORD
MFH Fan Assisted Heater
Serial No
Description
PO No
Reference No
Inspection Checklist
Status
Code
Name
Date
Comment
6 Monthly Inspection
01
Check equipment for external damage or signs of deterioration.
02
Check for dust build up or restricted air flow.
03
Check that impeller fittings are tight.
04
Check the impeller can spin unimpeded and that there is at least 2mm
clearance between blades and casing.
05
Clean the casing and impeller blades with a damp cloth.
06
Check that there is no dirt, debris, loose items or moisture within the
terminal enclosure
07
Check that all electrical connections are undamaged and tight
including any spare unused terminals.
08
Check the heaters/elements insulation resistance
09
Check that enclosure gaskets are undamaged and fitted correctly
10
Check that earth conductors are correctly fitted and undamaged
12 Monthly Inspection (in addition to 6 Monthly Inspections)
01
Check resistance values, including individual element resistance if it’s
down on IR
Motor Maintenance
01
3000 hours operation inspection of radial seal and re-application of
grease.
Carry out the inspection in accordance with relevant standards concerning inspection and
maintenance of electrical installations in non-hazardous or hazardous areas whichever is
applicable.
Verified
Installation
Energised
EXHEAT Industrial Ltd
Name
Signature
Date