Technical electrical connections (EXcon control
59/64
10.3.3 Analogue outputs
Master Aou1 (cooling)
• 0–10 V
Master Aou2 (heating)
• 0–10 V
Master Aou3 (heat recovery)
• 0–10 V
• Bypass damper motor 24 VAC (at 0 V the bypass is fully open)
10.3.4 Digital outputs
Master Dout1 (heating relay)
• Potential free relay. 230 VAC / 5A
• Circulation pump for heating
Master Dout2 (cooling relay)
• Potential free relay. 230 VAC / 5A
• Circulation pump for cooling
• Cooling unit
Master Dout3 (re-circulation relay)
• Damper control
Master Dout4 (A alarm relay output)
• Potential free relay max. 30 V / 3 A
• With A alarms, the air handling unit stops completely. Relay closes in case of an
alarm.
• Signal light
• BMS unit
Master Dout5 (B alarm relay output)
• Potential free relay max. 30 V / 3 A
• With B alarms, the air handling unit operates but there is a fault on some of the
functions. Relay closes in case of an alarm.
• Signal light
• BMS unit
Master Dout6 (operating relay)
• Potential free relay max. 30 V / 3 A