5.5.3 Cleaning the water coil (HW/CW/DX)
See the section "Removal of water coil" for description of how to remove the water
coil. (Applies to HW/CW)
NB:
If the coil is cleaned without removal, no water may be used unless there is a con-
densation tray under the coil (applies to CW/DX).
Step
Action
1
Clean the water coil with one of the following methods:
● Vacuum cleaning
● Blowing with air or steam flushing
● Flushing or rinsing with water
Please note! Take care when pressure washing not to damage the
fins.
2
Check that the fins on the heating coil are not deformed.
The fins are sharp.
3
Clean the condensation tray under the coil (for CW/DX)
5.5.4 Cleaning the condensation outlet
A condensation outlet with water trap must be established from the condensation
tray for the heat exchanger and cooling coil (option).
Step
Action
1
Check that the outlet and water trap function correctly by putting water
in the condensation tray
2
Clean the condensation tray
3005993-2021-03-09
Maintenance, hygiene and servicing
36/44
Содержание VEX300 Series