5. Maintenance, hygiene and servicing
5.1 Opening the VEX unit
The VEX unit's detachable panels must be opened to allow servicing and cleaning.
Removal of doors
Refer to the section on “Handling" for more information
5.2 Maintenance
Recommended in-
tervals
The following chart details the recommended maintenance intervals, under normal
operating conditions. EXHAUSTO recommends maintenance is adjusted to suit
the actual operating requirements.
5.2.1 Maintenance Schedule
Component
Procedure
Once
a year
Twice
a year
Filters*
Change when the display shows the filter alarm.
.
Recommended that both filters are replaced at the
same time.
NB:
The control system may give an 'early warning'
when a filter is becoming soiled, so that a new filter can
be obtained or a service fitter called
X
The filter should be changed at least
X
Filter monitor
Check that all the seals in the filter guide are tight.
X
Seals and sealing strips
Check that all the seals are tight.
X
Fans
For inspection, removal and cleaning of fan unit, see
section "Servicing" and "Cleaning"
X
Cooling/heating coil**
(HW/HE/CW/DX)
For inspection, removal and cleaning of the coil, see
section "Servicing" and "Cleaning"
X
Counterflow heat exchang-
er
For inspection, removal and cleaning of the counterflow
heat exchanger, see section "Servicing" and "Cleaning"
X
Condensation outlet
Inspection and cleaning of:
● Condensation outlet
● Condensation tray
● Water trap
See section "Cleaning"
X
Safety functions**
Inspection of:
● Fire thermostats
● Temperature sensors on heating pipe (accesso-
ries)
See instructions for the unit
X
Closing damper**
Function check
X
Motor valve and circulation
pump**
Function check
X
3005993-2021-03-09
Maintenance, hygiene and servicing
29/44