Temperature sensor
Unit
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the positioning of dampers, sen-
sors, air directions, etc.)
xx
yy
z
11
10
4
TE-RPT:
Return water pipe tem-
perature sensor on wa-
ter heating coil short-
circuited
TE-RPT:
●
Check the sensor's resistance complies with the actual temper-
ature. See temperature resistance table appendix 2.
●
If the sensor resistance has significantly changed in value, it
should be replaced.
11
11
4
TE-SPT:
Supply water pipe tem-
perature sensor on wa-
ter cooling coil discon-
nected
TE-SPT:
●
Check the sensor's resistance complies with the actual temper-
ature. See temperature resistance table appendix 2.
●
If the sensor resistance has significantly changed in value, it
should be replaced.
11
12
4
TE-SPT:
Supply water pipe tem-
perature sensor on wa-
ter cooling coil short-
circuited
TE-SPT:
●
Check the sensor's resistance complies with the actual temper-
ature. See temperature resistance table appendix 2
●
If the sensor resistance has significantly changed in value, it
should be replaced.
11
15
4
Tice
Supply water pipe tem-
perature sensor on wa-
ter cooling coil discon-
nected
Tice
●
Check the sensor's resistance complies with the actual temper-
ature. See temperature resistance table appendix 2.
●
If the sensor resistance has significantly changed in value, it
should be replaced.
11
16
4
Tice
Supply water pipe tem-
perature sensor on wa-
ter cooling coil short-
circuited
Tice
●
Check the sensor's resistance complies with the actual temper-
ature. See temperature resistance table appendix 2.
●
If the sensor resistance has significantly changed in value, it
should be replaced.
Fire thermostats
Unit
Fault code
Category
Unit
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the positioning of damp-
ers, sensors, air directions, etc.)
xx
yy
z
12
01
5
BT
FIRE:
Triggered fire alarm has
stopped VEX unit
In event of Fire: Follow the building emergency procedure
Fire thermostat triggered when there is no fire:
●
The closed circuit is broken. Find out why the fire detec-
tion unit has broken the circuit.
●
If no unit is connected – check jumper.
3004256-2014-09-10
Alarms
52/72