Menu 3.4 - Accessories
Ice-detect.
De-icing method
Heating coil >
Cooling unit >
Filter detect.
PIR >
TS >
CO2 >
RH >
3.4 Accessories
Tice
6
None
None
Timer
None
None
None
None
Line in Menu 3.4
Factory-set and
should not be
changed.
Comments
Ice detection method
●
Tice
De-icing method
Selected automatically:
●
Method 4, if a heating coil
is present
●
Method 6, if no heating coil
is present
Heating unit
Options:
●
None
●
MHCW (Water heating
coil)
*)
●
MHCE (Electric heating
coil)
●
IHCW (set at the factory
for the the EXact2 main
board, if the VEX was pur-
chased with HCW)
*) Not applicable to VEX308
Cooling unit
*)
Options:
●
None
*)
●
MXCU (external cooling
unit)
*)
●
CCW (cold water coil)
*)
●
CU (EXHAUSTO cooling
unit)
*)
*) Not applicable to VEX308
Filter detection
●
Hours
PIR
Activating PIR sensor. Op-
tions:
●
None
●
PIR1 (MIOPIR connected)
●
PIR2 (PIRB connected)
●
Both (Both MIOPIR and
PIRB connected)
When the sensor(s) is/are acti-
vated by movement in the
room, the VEX will be overrid-
den and set to comfort level.
Comfort level will be main-
tained for the time set on the
rear of the sensor (PIRB), after
which the VEX will return to the
previous indoor climate level.
NB: The time interval for MIO-
PIR is a fixed 10 minutes and
cannot be changed).
3004256-2014-09-10
Starting up the unit for operation
17/72