SGW1-IA3-MMP – Modbus Multiplexer
Exemys
www.exemys.com
SGW1-IA3-MMP User’s Manual Rev. 1
9
3.1
Master / Slave configuration parameters
Command
Description
MSCOM:
(M|S)(M|S)
(M|S)(M|S)
Configures if a Master or a Slave will be connected to the COM
• M
M
M
M = Master. / SSSS = Slave.
Example of use:
MSCOM
:
MMSM
(COM A, B and D connected to master devices, COM C connected to slave/s
device/s).
SLVTOUT:
(50..30000)
[ms]
Sets the maximum waiting time in the slave response.
This command applies to all ports connected to slaves.
NOTE:
NOTE:
NOTE:
NOTE: When the SGW1-IA3-MMP sends an order to the slave it expects a
response from the slave. If the slave does not respond within this time it will go to
the next master.
• Value = 50 ... 30000 [ms].
Example of use:
SLVTOUT:100
SLVTOUT
x
:
(50..30000)
[ms]
Sets the maximum waiting time in the response of the slaves connected to the X
port.
NOTE:
NOTE:
NOTE:
NOTE: When the SGW1-IA3-MMP sends an order to the slave it expects a
response from the slave. If the slave does not respond within this time it will go to
the next master.
• Value = 50 ... 30000 [ms].
Example of use:
SLVTOUT
A
:100
PRIORITY:
(0..100)
[ms]
Set the response priority level for all masters connected to the device.
NOTE:
NOTE:
NOTE:
NOTE: The priority of level 0 is the maximum. For each priority level added, extra
10 milliseconds are delayed before responding to that master's order.
This command applies to all ports connected to masters.
• Value = 0 ... 100 [ms].
Example of use:
PRIORITY:1
PRIORITY
x
:
(0..100)
[ms]
Sets the response priority level of the master connected to the X port.
NOTE:
NOTE:
NOTE:
NOTE: The priority of level 0 is the maximum. For each priority level added, extra
10 milliseconds are delayed before responding to that master's order.
• Value = 0 ... 100 [ms].
Example of use:
PRIORITY
B
:2