SGW1-IA3-MMP – Modbus Multiplexer
Exemys
www.exemys.com
SGW1-IA3-MMP User’s Manual Rev. 1
15
4
Typical Usage Modes
4.1
Multiplexer Mode
In this mode of use the SGW1-IA3-MMP allows up to 3 Modbus masters to query 1 or more
slaves simultaneously.
Example of configuration: 3 Masters and 1 Slave.
The first command that we should use is MSCOM and set Port A in slave mode and the other
ports master mode.
Then, if necessary, configure each particular port according to
its characteristics, as in the previous example.
With the BAUD, BITS, PARITY, STOP and PROTOCOL commands you can configure the
particular characteristics of each port. The team will perform conversions between one COM
and another if necessary.
It is important to take into account the response time of the slaves. This time can be set on
each port connected to slaves with the SLVTOUT command. Then you must set the response
time (timeout) on each of the master devices connected to the device. As a rule the master
timeout must be at least N times the timeout set in SGW1, N being the number of masters (1,
2 or 3)