3722-IG-002 Installation and User Manual
February 6, 2019
10
Electrical Service Connections
Note: Observe all required Lockout/Tagout procedures while making any electrical connections, or servicing the Model 3722
.
Caution
:
The two phases used must each
measure 120V to Neutral.
Earth Ground must be
connected to Neutral at only
one point, usually at the Service
Entry Breaker Panel.
Caution
:
This EVSE is a single-phase device. Do not
connect all 3 phases of a 3-phase feed!!! You
may use any two phases of a 3-phase, Wye-
connected feed ! The center-point of the 3
phases (usually used as Neutral) must be
grounded somewhere in the system. A current-
carrying Neutral is not needed by the Model
3722. The two phases used must each measure
120V to Neutral.
1)
220/240 VAC, Single Phase Transformer:
2) 208 VAC 3-Phase Wye Transformer:
Note: A 40 Amp. Non-GFCI breaker is required for the EVSE.
Model 3722-001
Figure 6A
(See
Fig.10)
Attention
:
Les deux phases utilisés doivent
chaque 120V mesure au Neutre.
Motif de la terre doit être
connecté au Neutre à un seul
point, habituellement à l'entrée de
Service Breaker Panel.
Attention
:
Cette EVSE est un appareil monophasé. Ne pas connecter tous les 3
phases d'un flux de phase 3!!! Vous pouvez utiliser tout deux phases
d'une phase 3, Wye connecté nourrir ! Le point central des 3 phases
(généralement utilisé comme Neutre) doit reposer quelque part dans le
système. Il n'est pas nécessaire de Neutre porteurs de courant par le
Modèle 3722. Les deux phases utilisés doivent chaque 120V mesure au
Neutre.
Figure 6B
Power Disconnect
Switch
Power Disconnect
Switch