2
preferably expel it externally into the atmosphere.
Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the
correct specification. At all times the manufacturer’s maintenance and service guidelines shall be
followed. If in doubt consult the manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
①
The charge size is in accordance with the room size within which the refrigerant containing
parts are installed;
②
The ventilation machinery and outlets are operating adequately and are not obstructed;
③
If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the
presence of refrigerant;
④
Marking to the equipment continues to be visible and legible. Markings and signs that are
illegible shall be corrected;
⑤
Refrigeration pipe or components are installed in a position where they are unlikely to be
exposed to any substance which may corrode refrigerant containing components, unless the
components are constructed of materials which are inherently resistant to being corroded or are
suitably protected against being so corroded.
Repairs to sealed components
DD.5.1
During repairs to sealed components, all electrical supplies shall be disconnected from
the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely
necessary to have an electrical supply to equipment during servicing, then a permanently
operating form of leak detection shall be located at the most critical point to warn of a potentially
hazardous situation.
DD.5.2
Particular attention shall be paid to the following to ensure that by working on electrical
components, the casing is not altered in such a way that the level of protection is affected. This
shall include damage to cables, excessive number of connections, terminals not made to original
specification, damage to seals, incorrect fitting of glands, etc.
Ensure that the apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded to the point that they no longer serve
the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in
accordance with the manufacturer’s specifications.
Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that
this will not exceed the permissible voltage and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while live in the presence
of a flammable atmosphere. The test apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer. Other parts may result in the
ignition of refrigerant in the atmosphere from a leak.
NOTE: The use of silicon sealant can inhibit the effectiveness of some types of leak detection
equipment.
Intrinsically safe components do not have to be isolated prior to working on them.
Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp
edges or any other adverse environmental effects. The check shall also take into account the
effects of aging or continual vibration from sources such as compressors or fans.
Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not
be used.
Leak detection methods
The following leak detection methods are deemed acceptable for systems containing flammable
Содержание evotherm EFI Ultra V30T
Страница 16: ...13 ...
Страница 18: ...15 ...
Страница 32: ...29 2 Account ID Password Login Existing accounts can be logged in directly in the following order ...
Страница 36: ...33 Step 5 When Scan devices Register on Cloud Initialize the device are all completed connect succeeds ...
Страница 42: ...39 Mode settings Click on the main interface to switch modes select what you need Timer setting ...
Страница 45: ...42 ...
Страница 47: ......
Страница 48: ......