![Evolution evotherm EFI Ultra V30T Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/evolution/evotherm-efi-ultra-v30t/evotherm-efi-ultra-v30t_installation-and-operation-manual_2446912028.webp)
25
Short running
Wire controller displays
actual water temperature,
no error code displays
1. Fan can’t run
2. Not enough air ventilation
3.Not enough refrigerant
1. Check the cable connections
between the motor and fan, if
necessary, they should be
replaced
2. Check the location of the heat
pump, and eliminate all
obstacles to assure a good air
ventilation
3 Replace or repair the heat
pump
water stains
Water stains on heat pump
unit
1. Condensed water
2. Water leakage
1. No action
2. Check the titanium heat
exchanger carefully if it shows
any defects
Too much ice
on evaporator
Too much ice on
evaporator
1. Check the location of heat
pump, and eliminate all
obstacles to assure a good air
ventilation
2. Replace or repair the heat
pump