CS-i Series Manual
Page 16
Syst2:Comp. IPM Over-temp.
Prot.
F255
Syst2 compressor running current is too
large
Check if there is a gap in the installation of the
fluorine-cooled heat sink
Syst2:Comp. Overcurrent Prot.
F256
Syst2 compressor drive board has poor
heat dissipation
Check if the pressure ratio is too high
Syst2:Comp. Bus Over Voltage
F257
Voltage is too high
Check if the input voltage is higher than 480V
Syst2:Comp. Bus Under Voltage
F258
Voltage is too low
Check if the input voltage is lower than 250V
Syst3:Inventer Board Comm.
Failure
F351
Communication failure with syst3
compressor drive board
1. Check if the communication line is normal
2. Check If the syst3 compressor drive board is
normal
Syst3:Compressor start Failure
F352
Syst3 compressor failed to start
1. Check if the compressor line is normal;
2. Check if the syst3 compressor is blocked
Syst3:Start IPM Prot.
F353
Syst3 compressor starting current is too
large
1. Check if the starting high pressure is
excessive;
2. Check if the syst3 compressor is blocked
Syst3:Running IPM Prot.
F354
Syst3 compressor running current is too
large
Check if the pressure ratio is too high
Syst3:Comp. IPM Over-temp.
Prot.
F355
Syst3 compressor running current is too
large
Check if there is a gap in the installation of the
fluorine-cooled heat sink
Syst3:Comp. Overcurrent Prot.
F356
Syst3 compressor drive board has poor
heat dissipation
Check if the pressure ratio is too high
Syst3:Comp. Bus Over Voltage
F357
Voltage is too high
Check if the input voltage is higher than 480V
Syst3:Comp. Bus Under Voltage
F358
Voltage is too low
Check if the input voltage is lower than 250V
Syst2:Inventer Board Comm.
Failure
F451
Communication failure with syst4
compressor drive board
1. Check if the communication line is normal
2. Check If the syst4 compressor drive board is
normal
Syst2:Compressor start Failure
F452
Syst4 compressor failed to start
1. Check if the compressor line is normal;
2. Check if the syst4 compressor is blocked
Syst2:Start IPM Prot.
F453
Syst4 compressor starting current is too
large
1. Check if the starting high pressure is
excessive;
2. Check if the syst4 compressor is blocked
Syst2:Running IPM Prot.
F454
Syst4 compressor running current is too
large
Check if the pressure ratio is too high
Syst2:Comp. IPM Over-temp.
Prot.
F455
Syst4 compressor running current is too
large
Check if there is a gap in the installation of the
fluorine-cooled heat sink
Syst2:Comp. Overcurrent Prot.
F456
Syst4 compressor drive board has poor
heat dissipation
Check if the pressure ratio is too high
Syst2:Comp. Bus Over Voltage
F457
Voltage is too high
Check if the input voltage is higher than 480V
Syst2:Comp. Bus Under Voltage
F458
Voltage is too low
Check if the input voltage is lower than 250V
Fan Motor 1 Output Out Phase
F101
System 1 fan failed to start
Check if the system 1 fan line is normal
Fan Motor 1 Output Zero Speed
F102
System 1 fan failed to start
Check if the system 1 fan rotor is locked
Fan Motor 1 Start IPM Prot.
F103
System 1 fan starting current is too large
Check if the system 1 fan rotor is locked
Fan Motor 1 Running IPM Prot.
F104
System 1 fan running current is too large
Check if the system 1 fan rotor is locked
Fan Motor 1 Overcurrent Prot.
F105
System 1 fan running current is too large
Check if the system 1 fan rotor is locked
Fan Motor 1 Over-temp. Prot.
F106
System 1 fan drive board has poor heat
dissipation
Check the heat dissipation condition
Fan Motor 1 Bus Over Voltage
F107
Voltage is too high
Check if the input voltage is higher than 480V
Fan Motor 1 Bus Under Voltage
F108
Voltage is too low
Check if the input voltage is lower than 250V
Fan Motor 2 Output Out Phase
F201
System 2 fan failed to start
Check if the system 2 fan line is normal
Fan Motor 2 Output Zero Speed
F202
System 2 fan failed to start
Check if the system 2 fan rotor is locked
Fan Motor 2 Start IPM Prot.
F203
System 2 fan starting current is too large
Check if the system 2 fan rotor is locked
Fan Motor 2 Running IPM Prot.
F204
System 2 fan running current is too large
Check if the system 2 fan rotor is locked
Fan Motor 2 Overcurrent Prot.
F205
System 2 fan running current is too large
Check if the system 2 fan rotor is locked
Fan Motor 2 Over-temp. Prot.
F206
System 2 fan drive board has poor heat
dissipation
Check the heat dissipation condition
Fan Motor 2 Bus Over Voltage
F207
Voltage is too high
Check if the input voltage is higher than 480V
Fan Motor 2 Bus Under Voltage
F208
Voltage is too low
Check if the input voltage is lower than 250V