CS-i Series Manual
Page 15
Syst4:Low pressure sensor Fault
PP41
The sensor is broken or short circuited
Check and change the pressure sensor
Syst1:High pressure sensor Fault
PP12
The sensor is broken or short circuited
Check and change the pressure sensor
Syst2:High pressure sensor Fault
PP22
The sensor is broken or short circuited
Check and change the pressure sensor
Syst3:High pressure sensor Fault
PP32
The sensor is broken or short circuited
Check and change the pressure sensor
Syst4:High pressure sensor Fault
PP42
The sensor is broken or short circuited
Check and change the pressure sensor
Syst1:High pressure prot.
E11
The high pressure switch of the system is
disconnected
Check the pressure switch of the system
Syst2:High pressure prot.
E21
The high pressure switch of the system is
disconnected
Check the pressure switch of the system
Syst3:High pressure prot.
E31
The high pressure switch of the system is
disconnected
Check the pressure switch of the system
Syst4:High pressure prot.
E41
The high pressure switch of the system is
disconnected
Check the pressure switch of the system
Syst1:Low pressure prot.
E12
The low pressure switch of the system is
disconnected
Check the pressure switch of the system
Syst2:Low pressure prot.
E22
The low pressure switch of the system is
disconnected
Check the pressure switch of the system
Syst3:Low pressure prot.
E32
The low pressure switch of the system is
disconnected
Check the pressure switch of the system
Syst4:Low pressure prot.
E42
The low pressure switch of the system is
disconnected
Check the pressure switch of the system
Syst1:4-way valve abnormal
switch
E121
The syst1 4-way valve switchover failed
Check if the 4-way valve reversing state is
required
Syst2:4-way valve abnormal
switch
E221
The syst2 4-way valve switchover failed
Check if the 4-way valve reversing state is
required
Syst3:4-way valve abnormal
switch
E321
The syst3 4-way valve switchover failed
Check if the 4-way valve reversing state is
required
Syst4:4-way valve abnormal
switch
E421
The syst4 4-way valve switchover failed
Check if the 4-way valve reversing state is
required
Syst1:Suction high temp. Prot.
E077
The suction temp. is high
Check the suction temp. is high or not
Syst2:Suction high temp. Prot.
E078
The suction temp. is high
Check the suction temp. is high or not
Syst3:Suction high temp. Prot.
E377
The suction temp. is high
Check the suction temp. is high or not
Syst4:Suction high temp. Prot.
E478
The suction temp. is high
Check the suction temp. is high or not
Syst1:Refrigerant leakage Prot.
E131
The refrigerant leakage
Check the system for refrigerant leakage
Syst2:Refrigerant leakage Prot.
E231
The refrigerant leakage
Check the system for refrigerant leakage
Syst3:Refrigerant leakage Prot.
E331
The refrigerant leakage
Check the system for refrigerant leakage
Syst4:Refrigerant leakage Prot.
E431
The refrigerant leakage
Check the system for refrigerant leakage
Anti-condensation prot.
E174
The condition of current air temp and inlet
water temp is cruel
Check the air temp and inlet water temp
Syst1:Inventer Board Comm.
Failure
F151
Communication failure with syst1
compressor drive board
1. Check if the communication line is normal
2. Check If the syst1 compressor drive board is
normal
Syst1:Compressor start Failure
F152
Syst1 compressor failed to start
1. Check if the compressor line is normal;
2. Check if the syst1 compressor is blocked
Syst1:Start IPM Prot.
F153
Syst1 compressor starting current is too
large
1. Check if the starting high pressure is
excessive;
2. Check if the syst1 compressor is blocked
Syst1:Running IPM Prot.
F154
Syst1 compressor running current is too
large
Check if the pressure ratio is too high
Syst1:Comp. IPM Over-temp.
Prot.
F155
Syst1 compressor running current is too
large
Check if there is a gap in the installation of the
fluorine-cooled heat sink
Syst1:Comp. Overcurrent Prot.
F156
Syst1 compressor drive board has poor
heat dissipation
Check if the pressure ratio is too high
Syst1:Comp. Bus Over Voltage
F157
Voltage is too high
Check if the input voltage is higher than 480V
Syst1:Comp. Bus Under Voltage
F158
Voltage is too low
Check if the input voltage is lower than 250V
Syst2:Inventer Board Comm.
Failure
F251
Communication failure with syst2
compressor drive board
1. Check if the communication line is normal
2. Check If the syst2 compressor drive board is
normal
Syst2:Compressor start Failure
F252
Syst2 compressor failed to start
1. Check if the compressor line is normal;
2. Check if the syst2 compressor is blocked
Syst2:Start IPM Prot.
F253
Syst2 compressor starting current is too
large
1. Check if the starting high pressure is
excessive;
2. Check if the syst2 compressor is blocked
Syst2:Running IPM Prot.
F254
Syst2 compressor running current is too
large
Check if the pressure ratio is too high
Содержание CS-i 250