background image

 

 

EvoHeat Advanced DHP-R Manual 

5.6 Rubber Feet 

All EvoHeat units are provided with rubber feet which EvoHeat highly recommend being installed. The rubber feet 

help reduce vibration of the unit and help provide a space below the heat pump to install the drainage barbs. 

 

 

5.7 Condensate Drain Barb 

Fit the condensate drain barb into the 2 holes under the unit if you 

need to direct water away from the heater. Put in hot water if stiff.  

 

 

5.8 Drainage & Condensation  

Whilst the heater is operating, water in the air condenses on the fins of the evaporator. In the instance of high 

humidity, the condensate may be several litres per hour. This may give the impression that the heater is leaking, 

however this is a normal function of heat pumps. 

The heater will automatically activate reverse cycle or de-icing mode when required which also increases condensate 

discharge. This normally occurs at temperatures below 8 degC. The condensate water will discharge through the 

base of the heater. As an option a pipe can be connected to the drain on the base of the unit to direct condensate 

water to an appropriate location. 

NOTE: A quick way to verify that the water is condensation is to shut off the unit and keep the pool pump running. If 

the water stops running out of the basepan, it is condensation. AN EVEN QUICKER WAY IS to TEST THE DRAIN WATER 

FOR CHLORINE – if the is no chlorine present, then it’s condensation. 

 

5.9 Plumbing 

The Swimming Pool Heat Pumps exclusive rated flow titanium heat exchanger requires no special plumbing 

arrangements except bypass (please set the flow rate according to the nameplate). The water pressure drop is less 

than 10kPa at max. 

Flow rate: Since there is no residual heat or flame Temperatures, the unit does not need copper heat sink piping. 

PVC pipe can be run straight into the unit. 

Location: Connect the unit in the pool pump discharge (return) line downstream of all filter and pool pumps, and 

upstream of any chlorinators, ozonators or chemical pumps. 

Standard model have slip glue fittings which accept 40 mm PVC pipe for connection to the pool or spa filtration 

piping. By using a 50 NB to 40NB you can plumb 40NB. 

Give serious consideration to adding a quick coupler fitting at the unit inlet and outlet to allow easy draining of unit 

for winterizing and to provide easier access should servicing be required. 

 

 

 

 

 

 

Содержание Advanced DHP-R Series

Страница 1: ......

Страница 2: ...___________________________________________________________________ 11 6 2 1 Start up Shut Down__________________________________________________________________________ 11 6 2 2 Switching Modes Setti...

Страница 3: ...y your pool at any time of the year with the powerful Evo Advanced DHP R Extremely energy efficient C O P up to 5 4 Available in 5 models 9kW to 26 9kW Low ambient air performance Heating and cooling...

Страница 4: ...3 EvoHeat Advanced DHP R Manual 2 Unit Dimensions DHP 20R DHP 30R DHP 40R DHP 50R Size mm A B C D E F G DHP 20R DHP 30R 680 645 720 422 663 686 40 DHP 40R DHP 50R 700 700 848 400 720 745 40 DHP 603R...

Страница 5: ...rubber pads under the feet of the unit 3 Install the supplied condensation barb to the underside of the unit and direct the condensation to an appropriate drainage point PLUMBING INSTALLATION PLEASE N...

Страница 6: ...display on the main screen to enter the parameter menu a Click the sun icon to activate heating mode b Click the temperature display to set the desired pool water temperature c Enter the temperature...

Страница 7: ...toppage the unit will not start for at least 3 minutes For unit cleaning or maintenance switch off and disconnect the power of the unit Do not install the unit near flammable gas or spray flammable su...

Страница 8: ...Location Recommendations Installation and service must be performed by a qualified installer Evo recommend the heat pump should be installed in an outdoor location with appropriate ventilation Install...

Страница 9: ...VOHEAT heat pumps have a factory preset internal water flow switch If there is insufficient water flow the heater will not operate It is CRITICAL that there is sufficient water flow to the unit Incorr...

Страница 10: ...ondensate water to an appropriate location NOTE A quick way to verify that the water is condensation is to shut off the unit and keep the pool pump running If the water stops running out of the basepa...

Страница 11: ...the installation location 4 The heater must be equipped with a circuit breaker and isolation device 5 Circuit breaker must be installed between the heater and the water circulation pump if the water p...

Страница 12: ...perature and power curve 8 Water Inlet Temperature Press to enter mode setting and the target temperature interface 9 LOCK Click to lock the screen To unlock press this button again and enter the code...

Страница 13: ...Name Button Colour Function 1 Timing Start Button Start Green End Grey Click this button to start or end the timing start setting function 2 Timing On Setting Click to set the start time of the timer...

Страница 14: ...urn off this setting once it reaches the end time 6 2 5 Fault History To view the fault records press 4 If there is no failure the main interface will display a static When a fault occurs the fault ic...

Страница 15: ...The ambient temp is low Secondary Anti freezing Prot E29 The ambient temp is low Inlet and oulet temp too big E06 Water flow is not enough and low differential pressure Check the pipe water flow and...

Страница 16: ...t voltage measurement Inv Sampling Volt F11 The input voltage sampling fault Check and adjust the current measurement Comm Err DSP PFC F12 DSP and PFC connect fault Check the communication connection...

Страница 17: ...et temperature set point 27 C Adjustable Heating the target temperature set point 27 C Adjustable Automatic target temperature set point 27 C Adjustable 7 2 Interface Drawing 7 2 1 Wire Control Interf...

Страница 18: ...ater input temperature input 14 AI DI07 Water output temperature input 15 AI DI08 System fan coil temperature input 16 AI DI09 Ambient temperature input 17 AI DI10 Mode switch input 18 AI DI11 Master...

Страница 19: ...18 EvoHeat Advanced DHP R Manual 8 2 PCB Description...

Страница 20: ...2 70mm2 250A 30mA less than 0 1 sec 186 224A 2 x 95mm2 95mm2 280A 30mA less than 0 1 sec Three Phase Unit Nameplate maximum current Phase line Earth line MCB Creepage Protector Signal Line No more tha...

Страница 21: ...nlet outlets often for leaks You should avoid the condition of no water or air entering into the system as this will influence unit s performance and reliability You should clear the pool spa filter r...

Страница 22: ...g or damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site b provide a copy of your r...

Отзывы: