F1
X3
X4
X5
X1
X2
EARTH
EARTH
L
N
MAINS
C
NO
NC
UFHV1
C
NO
NC
UFHV2
C
NO
NC
C
P1
C
P2
C
S1
S2
S3
C
C
C
Z1
Z2
C
A
B
C
A
A
C
B
B
C
24
BUS
ROOM CTRLR
J1
EXTERNAL TEMPERATURE
SENSORS
3.15 AMP
FUSE
OUTPUT 1
EXTERNAL MODBUS
ELECTRICAL METER
COMMUNICATION BUS RS485 SHIELD TWISTED PAIR
2 x 0.20mm²+shield (BELDEN 9501)
24
C
B
A
FROM
PREVIOUS
APARTMENT
TO
NEXT
APARTMENT
BUS TERMINATOR IF USING RS485
BUS FOR MASTER, CLOSE LINK
WITH JUMPER ONLY FOR THE
LAST BOARD IN THE LEG
OUTPUT 2
N
N
24
C
B
A
4 core x 0.33 mm²+shield (BELDEN 8723)
L
N E
1AMP
L
L
N
N
ZONE VALVE 1
HIU CONNECTION BOARD
L
N
N
L
N E
UNSWITCHED
FUSED SPUR
1AMP
L
L
N
N
ZONE VALVE 2
L
VOLT FREE INPUT
HEATING ENABLE
(ZONE 1)
X6
X7
VOLT FREE INPUT
HEATING ENABLE
(ZONE 2)
VOLT FREE OUTPUT
HIU COMMON ALARM
2 x 0.20mm²+shield (BELDEN 9501)
UNSWITCHED
FUSED SPUR
VIEWSMART
CONTROLLER / THERMOSTAT
(ZONE 1)
VIEWSMART
CONTROLLER / THERMOSTAT
(ZONE 2)
2 x 0.20mm²+shield (BELDEN 9501)
2 x 0.20mm²+shield (BELDEN 9501)
2 x 0.20mm²+shield (BELDEN 9501)
SEE NOTE 5
SEE NOTE 6
220/240 VOLTS (AC)
MAINS FROM UNSWITCHED
FUSE 3 AMP
COLD WATER
PULSE METER
2 x 0.20mm²+shield (BELDEN 9501) MAX 3 METRES
KEEP WARM FACILITY
OR DHW CYLINDER
SCHEDULES
OR 2ND PULSE METER
2 x 0.20mm²+shield (BELDEN 9501)
SEE NOTE 7
X6.1
X6.2
X6.3
X6.4
X6.5
X7.1
X7.2
X7.5
X7.3
X7.4
SEE NOTE 8
240 V CABLE
240 V CABLE
240 V CABLE
SEE NOTE 6
ZONE 1
ZONE 2
2 x 0.20mm²+shield (BELDEN 9501)
HIU CONTROL BOARD
SEE NOTE 9
RJ45
CAT 5e / CAT 6
SEE NOTE 9
TCP/IP COMMUNICATION
DRAWING No
CHECKED
TITLE
PROJECT
CLIENT
REV
DATE
REVISION
Evinox Energy Ltd.
Barwell Business Park
Leatherhead Road
Chessington
London KT9 2NY
Tel: 44 (0) 1372 722 277
Fax: 44 (0) 1372 744 477
DRAWN
DATE
SCALE
Evinox
www.evinox.co.uk
EVINOX RESERVES THE RIGHT TO MODIFY ANY CHARACTERISTICS OF ITS EQUIPMENT
WITHOUT PRIOR NOTICE AS PART OF ITS CONTINUING PRODUCT DEVELOPMENT
NOTES
TYPICAL WIRING
CONNECTION ARRANGEMENT
WITH TWO ROOM CONTROLLERS
AK
SEP 2018
N.T.S.
PL
STD/MOD/BMS
Electric wiring of MODUSAT and VIEWSMART
The MODUSAT connection board is inside the unit shall be connected
to the ViewSmart by means of a 4x0.33 sq mm + shield cable
(BELDEN 8723) having a max. length of 25m.
Shield Termination
The Screening on the bus communication cable (RS Part no
528-2106). Connect together and put in terminal 'C'
This screening must be connected to earth at the amplifier at the start
of the run. The screening must not be connected to anything at the
end of the run. This will enable any electrical disturbance to travel one
direction down the screening to earth.
External Pumps & Valves
Pumps & valves must have a localised power supply. Switched neutral
connection to be fitted with 1amp in-line fuse on live cable.
Termination
Bootlace ferrules to be used for connections to the connection board
and ViewSmart.
Heating
When Evinox ViewSmart is used, Z1-C and Z2-C connections not
needed. Z1-C and Z2-C only to be used for 3rd party controller to
enable heating. Other configurations are available.
Zone valves and second ViewSmart controller
Zone valves and a second ViewSmart controller are only needed when
two zone are used. Current Part L1A Building Regulations stipulate
that all new heating systems in dwellings that are not open plan and
with area greater than 150 m² must include at least two heating
zones, each controlled by a thermostat and zone valve.
Keep Warm Facility and DHW cylinder schedules
When Evinox ViewSmart is used, P2-C connection is not needed for
KWF control. P2-C only to be used for 3rd party controller to enable
Keep Warm Facility or DHW cylinder schedules. P2-C can also be used
for 2nd pulse meter.
Electricity Meter
Electricity consumption displayed on the ViewSmart. Extra credits
towards BREEAM.
RS-485 or TCP/IP Communication
Depending on the project specification RS-485 or TCP/IP
communication protocol can be used.
1.
2.
3.
4.
5.
6.
7.
8.
9.