9
2551988C
Use of Pre-installation Rig
A pre-installation rig is available upon request. It consists of a back panel constructed of steel. This
will enable the installer to arrange the piping entering and leaving the unit during first fix prior to the
unit being delivered / installed. The configuration of the pre-installation rig will be as per the unit
being supplied and the project requirements.
HOW TO INSTALL PRE-INSTALLATION RIG
STEP1: Securely fix the mounting
bracket to the wall in the required
position. Hang the ModuSat SPC Pre-
Installation Rig on the wall fixing
bracket. Then slide down by 15mm and
across to the right by 30mm, as
indicated in diagram.
STEP2: Fit the Evinox Energy Flushing
Bypass & Valve Kit to the rig and then
make final connections to the pipework
running to the ModuSat.
STEP3: Shut off isolation valves,
pressure test pipework and then
disconnect the valve unions.
STEP4: To remove the pre-installation
rig slide the rig to the left taking all
connections off centre, slowly lift and
remove.
Maintenance Space
In order to remove the ModuSat cooling interface unit, ensure that 30 mm gap is
left between the hook and the edge of the cutout in the pre-installation rig as
shown in the image below.
30 mm gap