29
Connecting Power
Connecting the Power Supply
Connect the positive end to the terminal 18 on the main module and the GND to
terminal 19 on the main module, as shown in Fig. 4.1.
V
+
V
-
Fig. 4.1 Connection to Power Supply
The voltage supply for EverAccess controller can handle a range of DC 9V ~18V.
The maximum current draw of the controller is 500 mA. If the backup battery is
connected to the controller, a power supply with DC15V output is required. The
power supply in the EverAccess enclosure is DC15V. In addition, the controller
provides a 12V power supply for the card readers. It should be noted that if a
controller powers multiple card readers, the current draw will be increased. The total
current draw can be calculated as below:
controller
to
connected
readers
reader
controller
number
current
Current
×
+
=
500
Important Tips:
The voltage supply should be located no more than 2
meters from the controller. Also, electric locks and alarm devices MUST be
powered separately. The controller’s power supply can power the controller
and modules, and the card readers, but NOT the locking hardware or alarm
devices.
Chapter
4
Main module
Содержание EFC-02-1A
Страница 72: ...64 cardholders individually or can do batch configurations if a group of cardholders share common properties...
Страница 73: ...65 Notes...
Страница 74: ......