EVER POWERLINE 31 UPS Range Operating Manual
21
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
SERVICE BYPASS Mode
When in this mode, the UPS unit can be serviced, without having to disconnect
receivers connected to its output.
CAUTION!
When the UPS unit is in SERVICE BYPASS mode, the
receivers powered from its output are not protected against power
losses in the input line in any way. In this mode the UPS unit is
completely disconnected from the output.
EMERGENCY Mode
or
Figure 9: EMERGENCY MODE
When EMERGENCY mode is on, the LCD panel displays an error code and emits
sound signals. Table 4 presents the explanation of error codes and sound signals.