EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
www.ever.eu
30
PARAMETERS \ TYPE
POWERLINE 31
POWERLINE 10-31
POWERLINE 15-31
POWERLINE 20-31
BATTERIES AND TYPICAL RUNTIME
Internal Batteries
None
External Batteries
1 x 20 VRLA 12V
External battery modules (EBM)
Yes
Maximum number of EBMs
2
Backup time
Depends on the type and number of batteries
Nominal voltage DC circuit
240 V DC
Maximum charging time - after discharging
at 80 % Pmax
Depends on the type and number of batteries
Maximum charging current
4 A
MECHANICAL SPECIFICATIONS
Dimensions (H x W x D)
717 x 260 x 570 mm
Net Weight
39 kg
55 kg
Gross Weight
49 kg
65 kg
Transport Dimensions (H x W x D)
1000 x 450 x 725 mm
Position in which devices transported
Vertical
PROTECT
Input over current protection
Short-circuit / Overload
–
Three-pole breaker
D50 A / 400 V AC
Short-circuit / Overload
– Three-pole breaker
D100 A / 400 V AC
Surge Protector
Output over current protection
Inverter working
– electronic short-circuit and overload protection
ACCESSORY AND EXTRA FUNCTIONS
Power supply connection
3P5W
screw terminals M8 (L, N, JP1, JP2)
screw terminals M6 (PE)
Output connection (number and type of
sockets )
1P3W
screw terminals M8 (L, N, JP1, JP2)
screw terminals M6 (PE)
EPO
Yes (NC)
Signalling
Acoustic and optical; LCD display
Communications interfaces
RS232, network management card SNMP / HTTP (optional),
AS 400 card - optional
Software
WinPower
CERTIFICATION
Declarations
CE
Standards
PN-EN 62040-1:2009, PN-EN 62040-2:2008
Notice: The manufacturer reserves the right to change the above listed parameters without notice.
ADDITIONAL NOTES:
1)
To ensure normal operation of the UPS unit, the load at its output should not exceed 80% of the value given in the chart. A
power reserve is necessary to maintain continuity of operation of connected appliances in case of momentary surges of load
current.
2)
With inter
nal batteries 5 ÷ 35 °C. Constant exposure of the device to environment temperature over +25°C results in reducing
battery life.
3)
Maximum allowed load the UPS unit will decrease as the altitude above the sea level increases over the specified limit.
4)
With prolonged operation with recommended load.