EVCO S.p.A. 

 

EVF 300 series | Installer manual ver. 1.3 | Code 144F300E134 

Page 1 of 62 

EVF 300 series  

Controllers for electric bread and pizza 

ovens, with touch-keys, in split version and 

which can be integrated into the unit. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installer manual| ENGLISH 

Code 144F300E134 

 

 

Содержание EVF 300 Series

Страница 1: ...aller manual ver 1 3 Code 144F300E134 Page 1 of 62 EVF 300 series Controllers for electric bread and pizza ovens with touch keys in split version and which can be integrated into the unit Installer ma...

Страница 2: ...fore use of the device and follow all recommendations keep this document with the device for future consultation Only use the device in the way described in this document do not use the same as a safe...

Страница 3: ...ary notes 25 9 2 Memorisation of a program 25 9 3 Starting a program 26 9 4 Interruption of a program 26 10 WEEKLY PROGRAMMED SWITCH ON FUNCTION 27 10 1 Preliminary notes 27 10 2 Setting the switch on...

Страница 4: ...e displays eleven touch keys and guarantees an IP65 protection rating for easy cleaning The controllers can independently manage the power supplied from the top and that supplied from the floor and th...

Страница 5: ...et EVF318 EVF328 110 0 x 250 0 mm 4 330 x 24 999 cm L x H 2custom 3 4 digit displays with function icon number of keys touch key 11 11 protection rating IP65 IP65 Control module without cover EVF318 E...

Страница 6: ...echanical relay technical compartment switch on off fan acoustic 8 A res 250 VAC electro mechanical relay 8 A res 250 VAC electro mechanical relay top 8 A res 250 VAC electro mechanical relay 12 V 30...

Страница 7: ...grammed switch on function energy saving function quick heating function configuration parameters access password restoring the factory settings For further information see chapter 19 TECHNICAL DATA T...

Страница 8: ...ing drawing illustrates the devices user interface dimensions these are expressed in mm in Installation is envisioned at the rear of the panel with biadhesive tape 2 2 Control module dimensions and in...

Страница 9: ...equipment containing powerful magnets large diffusers etc areas affected by direct sunlight rain humidity excessive dust mechanical vibrations or shocks any metal parts in proximity of the control mo...

Страница 10: ...configuration parameter u1 as follows extraction hood parameter u1 0 factory setting multifunction u1 1 The utility managed by the K5 digital output depends on the configuration parameter u11 as foll...

Страница 11: ...minal board if the device has been taken from a cold to hot place humidity could condense inside wait about 1 hour before powering it make sure that the power supply voltage the frequency and the devi...

Страница 12: ...tes the aspect of the devices user interface The following table illustrates the meaning of devices control module parts PART MEANING 1 communication port with the control module 2 termination resista...

Страница 13: ...ormation see the next chapters 4 2 Description of the control module The following drawing illustrates the aspect of the devices control module The following table illustrates the meaning of devices c...

Страница 14: ...EVCO S p A EVF 300 series Installer manual ver 1 3 Code 144F300E134 Page 14 of 62 10 TTL port 11 reserved 12 analogue inputs 13 reserved 14 RS 485 port and communication port with user interface...

Страница 15: ...raph 14 5 Setting the configuration parametersthe configuration parameters The following table illustrates the meaning of the configuration parameters the parameters are listed with the order accordin...

Страница 16: ...echnical compartment fan 1 switch on off 2 acoustic 0 Successively check that the remaining settings are appropriate see paragraph 14 7 List of configuration parameters 6 Connect to the electric mains...

Страница 17: ...weekly programmed switch on has been activated the top part of the UPPER display will be off If the device is off the top part of the UPPER display will be off 6 4 2 The bottom part of the UPPER displ...

Страница 18: ...rammed switch on function has been activated the bottom part of the LOWER display will be off If the device is off the bottom part of the LOWER display will be off 6 5 Silencing the buzzer Operate as...

Страница 19: ...switched on and that no other procedure is in progress 2 Hold the STEAM GENERATOR key down for 1 s the TON LED will flash and the bottom part of the LOWER display will show the flashing tOn time value...

Страница 20: ...n The time defined with the tOn parameter establishes the switch on duration of the injector and that defined with the tOF parameter that of switch off or for the entire duration that the key is press...

Страница 21: ...is off with the delay established with parameter u12 from device switch off 7 5 2 Output switch on off only if parameter u11 is set at 1 The activity of the output switch on off depends mainly on the...

Страница 22: ...meter r6 i e top set point r6 7 8 Chamber light 7 8 1 Preliminary notes Pressing and releasing the DOWN key will cause the chamber light to switch on until the key is pressed and released again or unt...

Страница 23: ...r count will be re proposed if vice versa the duration of the cut off is longer than the time established with parameter r13 on restoring the power supply the cooking timer count will be interrupted F...

Страница 24: ...1 Ensure that the device is switched on and that no other procedure is in progress 2 Press and release the START STOP key the TIMER LED will switch on and the bottom part of the UPPER display will sh...

Страница 25: ...number of steam injections in cyclic mode is envisioned among the settings memorised in the program and on program start up the generator is off these will be switched on and the method of consent on...

Страница 26: ...the program number will flash If no program is used the bottom part of the LOWER display will show flashing and the device displays will switch off 3 Press and release the UP or DOWN key within 15 s...

Страница 27: ...ours minutes Operate as follows to set the switch on day 1 Make sure that parameter r12 is set at 1 that programs are used that the device is off and that no procedure is in progress 2 Hold the PROGRA...

Страница 28: ...fore the operation is complete 13 Do not operate for 60 sec any changes will not be saved 10 3 Enabling the weekly programmed switch on function Operate as follows to activate the weekly programmed sw...

Страница 29: ...modification will not be saved Operate as follows to exit the procedure before the operation is complete 5 Press and release the ON STAND BY key or do not operate for 15 s any modifications will not...

Страница 30: ...nsure that the quick heating function is not in progress 2 Press and release the UP key the LED will switch on and the function will be activated until a key is pressed and released again or at maximu...

Страница 31: ...WN key within 15 s to set the value of the day Operate as follows to set the hours 4 Press and release the CLOCK key while setting the day of the week the hours value will flash 5 Press and release th...

Страница 32: ...fore the operation is complete 5 Do not operate for 15 sec any changes will be saved The working set point can also be set via parameter SP 14 3 Setting the top set point and the floor set point only...

Страница 33: ...le to set the floor set point via parameter SP2 14 4 Setting the power distributed at the top and that distributed at the floor only if the CFG parameter is set at 0 Operate as follows to set the powe...

Страница 34: ...ate for 15 sec any changes will be saved 14 5 Setting the configuration parameters Operate as follows to access the procedure 1 Make sure there is no cooking cycle or any procedure in progress 2 Hold...

Страница 35: ...g cycle or any procedure in progress 2 Hold the UP and DOWN key for 4 s the top part of the UPPER display will show PA 3 Press and release the TOP key or the FLOOR key the LOWER part of the display wi...

Страница 36: ...as follows to exit the procedure before the operation is complete 11 Hold the UP key and DOWN key down for 4 s before setting 1 i e before point 8 restore will not be performed Make sure that the man...

Страница 37: ...AM MIN MAX U M INP 1 INP 2 WORKING SET POINT SP r1 r2 C F 1 150 not dis working set point see also r0 SP1 r1 r2 C F 1 not dis 150 top set point see also r0 SP2 r7 r8 C F 1 not dis 150 floor set point...

Страница 38: ...type 0 thermocouple J 1 thermocouple K P2 0 1 0 0 temperature unit of measurement 2 0 C 1 F P4 0 2 2 2 steam injection activation consent mode 0 MANUAL steam injection will be allowed if the steam gen...

Страница 39: ...RAM MIN MAX U M INP 1 INP 2 MAIN REGULATOR r0 1 99 C F 1 5 5 if CFG 0 work set point differential of SP if CFG 1 top set point differential of SP1 r1 0 r2 C F 1 50 50 if CFG 0 minimum work set point i...

Страница 40: ...f injector switch on and tOF that of switch off or will cause steam injection for the entire duration the key is pressed t3 1 99 C F 1 5 5 SPS differential only if P4 2 t4 0 99 C F 1 50 50 temperature...

Страница 41: ...80 80 if CFG 0 cycle time for switch on of the top output and the floor output see also Po1 and Po2 if CFG 1 cycle time for switch on of the top output and the floor output during the energy saving f...

Страница 42: ...of the top above which the temperature alarm is activated code AH1 see also A3 8 A2 0 240 min 0 0 if CFG 0 temperature alarm display code AH1 if CFG 1 top temperature alarm delay code AH1 A3 0 2 0 0...

Страница 43: ...type of door micro switch input contact 0 normally open input active with closed contact 1 normally closed input active with open contact i5 0 1 1 1 effect caused by the activation of the multifuncti...

Страница 44: ...ed i16 0 1 0 0 type of electric absorption protection input contact 0 normally open input active with closed contact 1 normally closed input active with open contact PARAM MIN MAX U M INP 1 INP 2 DIGI...

Страница 45: ...d that established with the SPS parameter if steam injection is not allowed the STEAM INJECTION key will flash 5 During the energy saving function the top output and the floor output are switched on a...

Страница 46: ...d the activation mode of the steam injector will be AUTOMATIC PERSISTENT MANUAL TON switch on duration of the steam injector LED if it is on the value shown in the floor part of the LOWER display will...

Страница 47: ...ributed at the floor LED if it is on the value shown in the top part of the LOWER display will be the value of the power distributed at the floor if it flashes setting of the power distributed at the...

Страница 48: ...use temperature of the control module see parameter P7 when the cause of the alarm disappears press and release a key main consequences the device will be switched off the technical compartment fan wi...

Страница 49: ...power supply the cooking timer count will be re proposed if vice versa the duration of the cut off is longer than the time established with parameter r13 on restoring the power supply the cooking tim...

Страница 50: ...ept for the following alarms the use temperature alarm code Ht which requires a key to be pressed and released the power supply cut off alarm code PF which requires a key to be pressed and released th...

Страница 51: ...respect to the top probe main consequences the floor probe will function as top probe and as floor probe Pr2 floor probe error solutions the same as the preceding case but with respect to the floor p...

Страница 52: ...e main consequences if the alarm occurs when the device is on a cooking cycle cannot be started if the alarm occurs during a cooking cycle the cycle will be interrupted all outputs will be switched of...

Страница 53: ...te as follows to upload the device settings 1 Cut the device power supply off 2 Insert the EVKEY Micromatch connector into the device control module TTL serial port 3 Connect the device power supply t...

Страница 54: ...download operation requires several seconds If the operation is not completed successfully within this time period i e if the EVKEY signalling LED does not stop emitting red light and emitting green...

Страница 55: ...VIF20SUXI 3 Connect the device control module clamp of the RS 485 port to the removable screw terminal clamp of the RS 485 port of EVIF20SUXI 4 Connect the device control module shield clamp of the RS...

Страница 56: ...device power supply off 2 Disconnect the EVUSBREC01 power supply 3 Connect the device control module clamp of the RS 485 port to the EVUSBREC01 clamp of the RS 485 port 4 Connect the device control mo...

Страница 57: ...on flat surface with spacers Protection rating user interface control module IP65 IP00 Connections user interface control module fixed screw terminal board control module removable screw terminal boa...

Страница 58: ...ocouples thermocouple J type analogue inputs Type of sensor iron constantan Field of measurement from 99 to 8005 from 99 to 999 Resolution 1 C 1 F Protection none thermocouple K type analogue inputs T...

Страница 59: ...8 outputs of which 6 electro mechanical relays and 2 solid state relays in the EVF328 model 1 x 8 A res output 250 VAC electro mechanical relay SPST type K1 for steam injection management 1 x 8 A res...

Страница 60: ...r manual ver 1 3 Code 144F300E134 Page 60 of 62 Communication ports 2 ports 1 x TTL serial port for EVKEY programming 1 RS 48 serial port with MODBUS communication protocol for other EVCO products Sig...

Страница 61: ...16 Code 144F300E134 This document is exclusive property of EVCO EVCO does not assume any liability regarding possible errors stated The customer manufacturer installer or final user assumes all liabil...

Страница 62: ...EVCO S p A EVF 300 series Installer manual ver 1 3 Code 144F300E134 Page 62 of 62 EVCO S p A Via Mezzaterra 6 32036 Sedico Belluno ITALY Phone 39 0437 8422 Fax 39 0437 83648 info evco it www evco it...