ERRORS
17.1
Errors
The following table illustrates the meaning of the device error codes.
CODE
MEANING
Pr1
if the parameter CFG is set at 0, chamber probe error
solutions:
-
check that the probe is the thermocouple J or thermocouple K type
-
check the device-probe connection
-
check the temperature of the chamber
main consequences:
-
if the alarm occurs when the device is on, a cooking cycle cannot be started
-
if the alarm occurs during a cooking cycle, the cycle will be interrupted
-
the top output and the floor output will be switched off
if the parameter CFG is set at 1, top probe error
solutions:
-
the same as the preceding case but with respect to the top probe
main consequences:
-
the floor probe will function as top probe and as floor probe
Pr2
floor probe error
solutions:
-
the same as the preceding case but with respect to the floor probe
main consequences:
-
the top probe will function as top probe and as floor probe
Pr3
steam probe error
solutions:
-
the same as the preceding case but with respect to the steam probe
main consequences:
-
if parameter P4 is set at 2, steam injection will be disabled and the steam generator will be
switched off
E0C
cold joint error
solutions:
-
cut the device power supply off
main consequences:
-
if the error occurs when the device is on, a cooking cycle cannot be started
-
if the error occurs during a cooking cycle, the cycle will be interrupted
-
all outputs will be switched off
rtc
clock error
solutions:
-
set the day of the week and the time
main consequences:
-
the “weekly programmed switch-on” function will not be available