EVC30S40 / EVC70S40 

2 output digital modules for electric bread and pizza ovens

version 1.02

E

ENGLISH

1

IMPORTANT

1.1

Important

Read these instructions carefully before installation and commissioning and follow all recommendations for installation and for the electric
connection; keep these instructions with the instrument for future consultation.

The instrument must be disposed of according to local Standards regarding electric and electronic appliances.

2

DIMENSIONS AND INSTALLATION

2.1

Dimensions and installation

Dimensions in mm (in); back-panel installation using M3 studs.
The diagram illustrates the model with the greatest supply of hardware.

2.2

Recommendations for installation

• make sure that the working conditions (temperature of use, humidity, etc.) lie within the limits indicated in the technical data
• do not install the instrument in proximity of heat sources (heaters, hot air pipes etc.) appliances withe strong magnets (large diffusers etc.), places

subject to direct sunlight, rain, humidity, excessive dust, mechanical vibrations or shocks

• in compliance with Safety Standards, the protection against any contact with the electric parts must be ensured via correct installation of the

instrument. All parts that ensure protection must be fixed in a way such that they cannot be removed without the aid of a tool.

3

ELECTRIC CONNECTION

3.1

Electric connection

The diagram illustrates the model with the greatest supply of hardware.

3.2

Recommendations for installation

• do not operate on the terminal boards using electric or pneumatic

screwdrivers

• if the instrument has been taken from a old place to a hot one, the

humidity could condense inside. Wait about one hour before
applying power

• make sure that the power supply voltage, frequency and operational

electric power correspond to those of the local power supply

• disconnect the power supply before performing any type of

maintenance

• equip the probes with a protection able to insulate them against any

contact with metal parts or use isolated probes

• do not use the instrument as a safety device
• for repairs and information regarding the instrument, contact the

Evco sales network.

4

MODELS AVAILABLE

4.1

Models available

With reference to the electric connection illustrated in paragraph 3.1.

CODE

FUNCTION

PROBE 1

PROBE 2

LOAD 1

LOAD 2

NUMBER OF KEYS

(ENCODER YES/NO)

EVC30S40J7XXX00

simple regulation

chamber probe

not used

regulation of the

not used

0

of the temperature

temperature

(yes)

EVC30S40J7XXX01

simple regulation

chamber probe

not used

regulation of the

auxiliary

4

of the temperature

temperature

(no)

EVC30S40J7XXX02

top-floor

top probe

floor probe

top

floor

4

 regulation

(no)

of the temperature

EVC30S40J7XXX03

top-floor

top probe

floor probe

top

floor

6

regulation

(no)

of the temperature

EVC30S40J7XXX04

top-floor

top probe

floor probe

top

floor

0

regulation

(yes)

of the temperature

EVC30S40J7XXX05

top-floor

top probe

floor probe

top

floor

2

regulation

(yes)

of the temperature

EVC70S40X7XXX00

cooking timer

not used

not used

acoustics

not used

4

(no)

EVC70S40X7XXX01

steam injection

not used

not used

timer 1

timer 2

4

(no)

EVC70S40X7XXX02

steam injection

not used

not used

timer 1

timer 2

6

(no)

EVC70S40X7XXX03

cooking timer

not used

not used

acoustics

not used

0

(yes)

4.2

Management of the utilities

Temperature regulation.
The output activity depends mainly on the temperature of the
chamber, the work set point and the parameter P5.
Top.
If functioning with 1 measurement input (parameter P3 = 1):
• the out put is measured in a cyclical mode, preferably when the floor

output is off (the parameter P10 establishes the cycle time. Using the
procedure given in paragraph 6.2.1 it is possible to set the duration
of output switch-on, intended as a percentage of the time established
with the parameter P10)

• the cyclical activation is subordinate to the temperature of the

chamber (chamber probe), at the work set point and parameter P4.

If functioning with 2 measurement inputs (parameter P3 = 0):
• the output activity will mainly depend on the temperature of the top

(top probe), the top set point and the parameter P4.

Floor.
If functioning with 1 measurement input (parameter P3 = 1):
• the out put is measured in a cyclical mode, preferably when the top

output is off (the parameter P10 establishes the cycle time. Using the
procedure given in paragraph 6.2.2 it is possible to set the duration
of output switch-on, intended as a percentage of the time established
with the parameter P10)

• the cyclical activation is subordinate to the temperature of the

chamber (chamber probe), at the work set point and parameter P4.

If functioning with 2 measurement inputs (parameter P3 = 0):
• the output activity will mainly depend on the temperature of the

floor (floor probe), the floor set point and the parameter P4.

Timer 1.
The output is on continuously during the count of the time P0.
Timer 2.
The output is on continuously during the count of the time P6.
Acoustics.
The output is on continuously on the conclusion of the count of
the cooking timer.
Auxiliary.
The activity of the output depends mainly on parameters P6 and P7.

5

USER INTERFACE

5.1

Preliminary considerations

The diagram illustrates the model with the greatest supply of hardware.

For all models.
The following functioning states exist:
• the “on” status (the instrument is powered and “on”: the regulators

can be switched on)

• the “stand-by” status (the instrument is powered but is “off” via software:

the regulators are off

• the “off” state (the instrument “is not powered”).
Successively, the term “switch-on” means that the passage from the
stand-by status to the on status; the term “switch-off” means the passage
from the on status to the stand-by status.
When the instrument is powered it re-proposes the status in which it
found itself at the time when the power supply was disconnected.
If there is a power cut during a time count, the count will start again
from the beginning when the power supply is restored.

5.2

Switching the instrument on

For EVC30S40J7XXX01 / 02 / 03 and for EVC70S40X7XXX00 / 01 / 02.
• make sure no procedure is in progress
• press

B1

: the 

L4

 LED will switch-off.

For EVC30S40J7XXX00 / 04 / 05 and for EVC70S40X7XXX03.
• make sure no procedure is in progress
• press the encoder button: the 

L4

 LED will switch-off.

5.3

Switching the instrument off

For EVC30S40J7XXX01 / 02 / 03 and for EVC70S40X7XXX00 / 01 / 02.
• make sure no procedure is in progress
• press

B1

for 4 s: the 

L4

 LED will switch-on.

For EVC30S40J7XXX00 / 04 / 05 and for EVC70S40X7XXX03.
• make sure no procedure is in progress
• press the encoder button for 4 s: the 

L4

 LED will switch-on.

5.4

The display

For EVC30S40J7XXX00 / 01.
If the instrument is on, the display will show the size established with
parameter P10:
• if P10 = 0, the display will show the work set point
• if P10 = 1, the display will show the chamber temperature
If the instrument is off:
• the display will be off
• the 

L4

 LED will be on

Содержание EVC30S40

Страница 1: ... regulation The output activity depends mainly on the temperature of the chamber the work set point and the parameter P5 Top If functioning with 1 measurement input parameter P3 1 the out put is measured in a cyclical mode preferably when the floor output is off the parameter P10 establishes the cycle time Using the procedure given in paragraph 6 2 1 it is possible to set the duration of output sw...

Страница 2: ...g the floor set point For EVC30S40J7XXX02 if the parameter P3 is set at 0 make sure that the instrument is in on status and that no procedure is in progress press B5 the display shows the corresponding value and the L2 LED will flash press B2 or B5 within 15 s see also parameters P5 P6 and P8 do not operate for 15 s the L2 LED will switch off and the instrument will exit the procedure To exit the ...

Страница 3: ...2 the L1 LED switches off and the L2 LED will flash press B2 or B5 within 15 s see also parameters P6 P7 and P8 press B1 the display will show the time t3 the L2 LED switches off and the L3 LED will flash press B2 or B5 within 15 s see also parameters P3 P4 and P5 press B1 the instrument will exit the procedure and L3 LED will switch off To exit the procedure in advance do not operate for 15 s any...

Страница 4: ... deactivated For EVC30S40J7XXX02 03 04 05 if the parameter P3 is set at 1 chamber probe error Solutions the same as the previous case but relative to the chamber probe Main consequences the top output and the floor output will be deactivated AL2 For EVC30S40J7XXX02 03 04 05 if parameter P3 is set at 0 floor probe error Solutions the same as the previous case but relative to the floor probe Main co...

Страница 5: ...t differential if P3 0 minimum top set point and floor set point if P3 1 minimum work set point firmware code 3 time t3 maximum value enabling of the use temperature alarm code H t 1 YES duration of auxiliary output switch on see also P7 if P3 0 maximum top set point and floor set point if P3 1 maximum work set point firmware version code 3 time t2 predefined value temperature over which the use t...

Страница 6: ...dified DESCRIPTION predefined value of the power supplied at the floor percentage of P10 only if P3 1 see also P9 firmware code 3 enabling of the use temperature alarm code H t 1 YES firmware version code 3 temperature over which the use temperature alarm is activated code H t see also P14 firmware revision code 3 size displayed when the instrument is on 0 if P3 0 top temperature if P3 1 chamber t...

Отзывы: