background image

7

Operation and Maintenance Instructions

2.  Two Speed Motors

 

The use of a two-speed motor provides an additional step 
of capacity control when used with the fan cycling method. 
The low speed of the motor will provide approximately 
60% of full speed capacity. 

 

Two-speed capacity control systems require not only a two-
speed motor, but also a two-stage thermostat and the proper 
two-speed motor starter. 

 

It is important to note that when two-speed motors are to 
be used, the motor starter controls must be equipped with 
a decelerating time delay relay. The time delay should be a 
minimum of a 30 second delay when switching from high 
speed to low speed.

3.  Variable Frequency Drives

 

The use of a variable frequency drive (VFD) provides the 
most precise method of capacity control. A VFD is a 
device that converts a fixed AC voltage and frequency into 
an adjustable AC voltage and frequency used to control 
the speed of an AC motor. By adjusting the voltage and 
frequency, the AC induction motor can operate at many 
different speeds. 

 

VFD technology has particular benefit on evaporative 
cooling units operating in cold climates where airflow can 
be modulated to minimize icing and reversed at low speed 
for de-icing cycles. Applications using a VFD for capacity 
control must also use an inverter capable motor built in 
compliance with NEMA standard MG-1.

 

The VFDs need to have a pre-set shutoff to prevent water 
temperatures from becoming too cold and to prevent 
the drive from trying to turn the fan at near zero speed. 
Operating below 25% of motor speed achieves very little 
return in fan energy savings and capacity control. Check 
with your VFD supplier if operating below 25% is possible.

NOTE

:

 Pump Motors: VFD’s should not be used on pump 

motors. The pumps are designed to be operated at full 
speed and are not intended to be used as capacity control.

The type of motor, manufacturer of the VFD, motor lead 
lengths (between the motor and the VFD), conduit runs and 
grounding can dramatically affect the response and life of 
the motor. Select a high quality VFD that is compatible with 
the fan motor(s) in the EVAPCO unit(s). Many variables in 
the VFD configuration and installation can affect motor and 
VFD performance. Two particularly important parameters 
to consider when choosing and installing a VFD are 
switching frequency and the distance between the motor 
and VFD often referred to as lead length. Consult the VFD 
manufacturer’s recommendations for proper installation 
and configuration. The motor lead length restrictions 
can vary with the vendor. Regardless of motor supplier, 
minimizing lead length between the motor and drive is 
good practice.

VFD Lockout Notification

Sequence of Operations / Guidelines for Multi-fan Units with a 
VFD during Peak Load

For eco-ATWE, see Sage

2

/Sage

3

 control Panel O&M:

1.  Both fan motors off – Pump running on one cell.
2.  Both fan motors off – Pump running on both cells.
3.  Both VFDs turn on at the manufacturer’s recommended 

minimum operating speed (25%) – Pump running on both 
cells.

4.  Both VFDs speed up uniformly (they should be 

synchronized on start-up) – Pump running on both cells.

5.  Both VFDs are on full speed – Pump running on both cells.

NOTE

:

 The VFDs need to have a preset shutoff to prevent 

water temperatures from becoming too cold and to prevent 
the drive from trying to turn the fan at near zero speed. 
Operating below 25% of motor speed achieves very little 
return in fan energy savings and capacity control. Check with 
your VFD supplier if operating below 25% is possible.

Содержание ATC-E

Страница 1: ...Box 1300 Westminster Maryland 21158 USA Phone 410 756 2600 Fax 410 756 6450 EVAPCO Europe bvba Heersterveldweg 19 Industrieterrein Oost 3700 Tongeren Belgium Phone 32 12 395029 Fax 32 12 238527 evapc...

Страница 2: ...A lock out tag out procedure integrated with the Process Control System must be foreseen by the customer A lockable disconnect switch should be located within sight of the unit for each fan motor ass...

Страница 3: ...could potentially cause damage to plastic components Label on the coil section s WARNING Do not operate the pressure vessel at service conditions outside of the PED nameplate located at the coil conne...

Страница 4: ...d minimum speeds and for recommendations on locking out resonance frequencies 5 Verify that a water treatment plan has been implemented including passivation of galvanized steel units See Water Treatm...

Страница 5: ...e fully opened before the pumps turn on If the system temperature continues to rise the unit fan is cycled on For a variable speed controller the fans are turned on to minimum speed See the Fan System...

Страница 6: ...38 C Regal R O 220 DTE Oil BB Teresstic 220 All bearings used on EVAPCO equipment are factory adjusted and self aligning Do not disturb bearing alignment by tightening the sleeve bearing caps Fan Bel...

Страница 7: ...if operating below 25 is possible NOTE Pump Motors VFD s should not be used on pump motors The pumps are designed to be operated at full speed and are not intended to be used as capacity control The t...

Страница 8: ...to minimum speed Should vibration inducing frequencies exist the run up and run down test will isolate the resonant frequencies which then must then be locked out in the VFD programming Two Speed Moto...

Страница 9: ...e is a bronze valve connected to a float arm assembly and is activated by a large foam filled plastic float The float is mounted on an all thread rod held in place by wing nuts The water level in the...

Страница 10: ...p When Supplied The pump and pump motor should be lubricated and serviced in accordance with the pump manufacturer s instructions The recirculation pump should not be used as a means of capacity contr...

Страница 11: ...f operation During this passivation period recirculating water pH should be maintained above 7 0 and below 8 0 at all times Since elevated temperatures have a harmful effect on the passivation process...

Страница 12: ...oling equipment can be considered as long as the resultant recirculating water chemistry conforms to the parameters noted in Table 3 It should be noted that using water reclaimed from other processes...

Страница 13: ...10 x24 20 x12 10 x18 10 x36 20 x18 12 x12 12 x14 12 x18 12 x24 12x28 12 x36 24 x12 24 x14 24 x18 24 x24 24 x28 24 x36 12 x20 12 x40 24 x20 24 x40 2 0 2 0 2 0 2 0 3 0 4 0 2 5 2 5 3 7 5 7 3 5 2 5 3 0 2...

Страница 14: ...ith a remote sump is an excellent way of reducing unit capacity at low temperatures Other methods of capacity control include two speed motors VFDs and fan cycling These can be used individually or in...

Страница 15: ...ser during the winter is to run the unit DRY In dry operation the recirculation pump is turned off the basin drained and air passes over the coil Instead of using evaporative cooling to cool the proce...

Страница 16: ...ethod of managing the amount of ice buildup is by cycling the fan motors off while keeping the pump on During these periods of idle fan operation the warm water that is absorbing the building load flo...

Страница 17: ...crape and coat with ZRC annually 10 Lubricate fan shaft bearings every 1000 hours of opera tion or every three months 11 Lubricate fan motor bearings see mfg s instructions Typi cally for non sealed b...

Страница 18: ...robe ends of scale build up quarterly 12 Electronic Water Level Controller Clean inside the standpipe annually 13 Solenoid Make up Valve Inspect and clean valve of debris as needed 14 Vibration Switch...

Страница 19: ...ned at least once a month by hand This can be accomplished by making sure the unit s disconnect is tagged and locked out and grasping the fan assembly rotating it several turns 9 Energize fan motor sp...

Страница 20: ...2013 EVAPCO Europe Bulletin 116R E Metric 0322 Operation and Maintenance Instructions...

Отзывы: