background image

12

Operation and Maintenance Instructions

If a chemical water treatment program is used, all chemicals 
selected must be compatible with the unit’s materials of 
construction as well as other equipment and piping used 
in the system. Chemicals should be fed through automatic 
feed equipment to a point which ensures proper control and 
mixing prior to reaching the evaporative cooling equipment.  
Chemicals should never be batch fed directly into the basin of 
the evaporative cooling equipment.

Evapco does not recommend the routine use of acid due to 
the destructive consequences of improper feeding; however, 
if acid is used as part of the site specific treatment protocol, 
it should be pre-diluted prior to introduction into the cooling 
water and fed by automated equipment to an area of the 
system which ensures adequate mixing.  The location of the 
pH probe and acid feed line should be designed in conjunction 
with the automated feedback control to ensure that proper 
pH levels are consistently maintained throughout the cooling 
system.  The automated system should be capable of storing 
and reporting operational data including pH reading and 
chemical feed pump activity.  Automated pH control systems 
require frequent calibration to ensure proper operation and to 
protect the unit from increased corrosion potential.

The use of acids for cleaning should also be avoided.  If acid 
cleaning is required, extreme caution must be exercised and 
only inhibited acids recommended for use with the unit’s 
materials of construction should be used.  Any cleaning 
protocol, which includes the use of an acid, shall include a 
written procedure for neutralizing and flushing the evaporative 
cooling system at the completion of the cleaning. 
Flume/equalizer DO NOT ensure proper controlled mixing of 
water in multiple cells. Operate multiple cells individually.

Control of Biological Contamination

Evaporative cooling equipment should be inspected regularly 
to ensure good microbiological control.  Inspections should 
include both monitoring of microbial populations via culturing 
techniques and visual inspections for evidence of biofouling.  

Poor microbiological control can result in loss of heat transfer 
efficiency, increase corrosion potential, and increase the 
risk of pathogens such as those that cause Legionnaires’ 
disease.  The site specific water treatment protocol should 
include procedures for routine operation, startup after a shut-
down period, and system lay-up, if applicable.  If excessive 
microbiological contamination is detected, a more aggressive 
mechanical cleaning and/or water treatment program should 
be undertaken.  

It is important that all internal surfaces, particularly the basin, 
be kept clean of accumulated dirt and sludge.  Additionally, 
drift eliminators should be inspected and maintained in good 
operating condition.

Gray Water and Reclaimed Water

The use of water reclaimed from another process as a 
source of makeup water for evaporative cooling equipment 
can be considered as long as the resultant recirculating 
water chemistry conforms to the parameters noted in 
Table 3. It should be noted that using water reclaimed from 
other processes may increase the potential of corrosion, 
microbiological fouling, or scale formation.  Gray water or 
reclaimed water should be avoided unless all of the associated 
risks are understood and documented as part of the site 
specific treatment plan.

Air Contamination

Evaporative cooling equipment draws in air as part of normal 
operation and can scrub particulates out of the air.  Do not 
locate the unit next to smokestacks, discharge ducts, vents, 
flue gas exhausts, etc. because the unit will draw in these 
fumes which may lead to accelerated corrosion or deposition 
potential within the unit.  Additionally, it is important to locate 
the unit away from the building’s fresh air intakes to prevent 
any drift, biological activity, or other unit discharge from 
entering the building’s air system.

Cold Weather Operation & Ice Management

EVAPCO counterflow evaporative cooling equipment is well 
suited to operate in cold weather conditions. The counterflow 

design encases the heat transfer media (fill and/or coils) 
completely, and protects it from the outside elements such as 
wind which can cause freezing in the unit. 

When the evaporative cooling unit is going to be used during 
cold weather conditions, several items need to be considered 
including unit layout, recirculating water, unit recirculating 
piping, unit heat transfer coils, unit accessories and capacity 
control of the units. 

More information can be found in Bulletin 116-E, pages 21-26.

 

Freeze Protection of Recirculating Water

The simplest and most effective way of keeping the 
recirculated water from freezing is to use a remote sump.  
With a remote sump, the recirculating water pump is 
mounted remotely at the sump and whenever the pump 
is shut off, all recirculating water drains back to the sump.  
Recommendations for sizing the remote sump tank and 
recirculating water pumps for coil products are presented 
for Evaporative Condensers and Closed Circuit Coolers in 
their respective catalog. The pressure drop through the water 
distribution system measured at the water inlet is as follows in 

Table 4 

(See next page).

If a remote sump cannot be used, basin heaters are available 
to keep the recirculating water from freezing when the pump 
is turned off. Electric heaters may be used to heat the basin 
water when the unit is shut down. The make-up water supply, 
overflow and drain lines, as well as the pump and pump piping 
up to the overflow level must be heat traced and insulated 
to protect them from damage. Any other connections or 
accessories at or below the water level, such as electronic 
water level controllers, must also be heat traced and insulated. 

Note: Using basin heaters will not prevent the fluid in the 

coils, nor the residual water in the pump or pump piping 

from freezing.

A condenser or cooler cannot be operated dry (fans on, pump 
off) unless the water is completely drained from the pan.  The 
pan heaters are sized to prevent pan water from freezing only 
when the unit is completely shut down.

Содержание ATC-E

Страница 1: ...Box 1300 Westminster Maryland 21158 USA Phone 410 756 2600 Fax 410 756 6450 EVAPCO Europe bvba Heersterveldweg 19 Industrieterrein Oost 3700 Tongeren Belgium Phone 32 12 395029 Fax 32 12 238527 evapc...

Страница 2: ...A lock out tag out procedure integrated with the Process Control System must be foreseen by the customer A lockable disconnect switch should be located within sight of the unit for each fan motor ass...

Страница 3: ...could potentially cause damage to plastic components Label on the coil section s WARNING Do not operate the pressure vessel at service conditions outside of the PED nameplate located at the coil conne...

Страница 4: ...d minimum speeds and for recommendations on locking out resonance frequencies 5 Verify that a water treatment plan has been implemented including passivation of galvanized steel units See Water Treatm...

Страница 5: ...e fully opened before the pumps turn on If the system temperature continues to rise the unit fan is cycled on For a variable speed controller the fans are turned on to minimum speed See the Fan System...

Страница 6: ...38 C Regal R O 220 DTE Oil BB Teresstic 220 All bearings used on EVAPCO equipment are factory adjusted and self aligning Do not disturb bearing alignment by tightening the sleeve bearing caps Fan Bel...

Страница 7: ...if operating below 25 is possible NOTE Pump Motors VFD s should not be used on pump motors The pumps are designed to be operated at full speed and are not intended to be used as capacity control The t...

Страница 8: ...to minimum speed Should vibration inducing frequencies exist the run up and run down test will isolate the resonant frequencies which then must then be locked out in the VFD programming Two Speed Moto...

Страница 9: ...e is a bronze valve connected to a float arm assembly and is activated by a large foam filled plastic float The float is mounted on an all thread rod held in place by wing nuts The water level in the...

Страница 10: ...p When Supplied The pump and pump motor should be lubricated and serviced in accordance with the pump manufacturer s instructions The recirculation pump should not be used as a means of capacity contr...

Страница 11: ...f operation During this passivation period recirculating water pH should be maintained above 7 0 and below 8 0 at all times Since elevated temperatures have a harmful effect on the passivation process...

Страница 12: ...oling equipment can be considered as long as the resultant recirculating water chemistry conforms to the parameters noted in Table 3 It should be noted that using water reclaimed from other processes...

Страница 13: ...10 x24 20 x12 10 x18 10 x36 20 x18 12 x12 12 x14 12 x18 12 x24 12x28 12 x36 24 x12 24 x14 24 x18 24 x24 24 x28 24 x36 12 x20 12 x40 24 x20 24 x40 2 0 2 0 2 0 2 0 3 0 4 0 2 5 2 5 3 7 5 7 3 5 2 5 3 0 2...

Страница 14: ...ith a remote sump is an excellent way of reducing unit capacity at low temperatures Other methods of capacity control include two speed motors VFDs and fan cycling These can be used individually or in...

Страница 15: ...ser during the winter is to run the unit DRY In dry operation the recirculation pump is turned off the basin drained and air passes over the coil Instead of using evaporative cooling to cool the proce...

Страница 16: ...ethod of managing the amount of ice buildup is by cycling the fan motors off while keeping the pump on During these periods of idle fan operation the warm water that is absorbing the building load flo...

Страница 17: ...crape and coat with ZRC annually 10 Lubricate fan shaft bearings every 1000 hours of opera tion or every three months 11 Lubricate fan motor bearings see mfg s instructions Typi cally for non sealed b...

Страница 18: ...robe ends of scale build up quarterly 12 Electronic Water Level Controller Clean inside the standpipe annually 13 Solenoid Make up Valve Inspect and clean valve of debris as needed 14 Vibration Switch...

Страница 19: ...ned at least once a month by hand This can be accomplished by making sure the unit s disconnect is tagged and locked out and grasping the fan assembly rotating it several turns 9 Energize fan motor sp...

Страница 20: ...2013 EVAPCO Europe Bulletin 116R E Metric 0322 Operation and Maintenance Instructions...

Отзывы:

Похожие инструкции для ATC-E