Operation and Maintenance Instructions

Freeze Protection of Closed Circuit Cooler Coils

The simplest and most effective way of protecting the heat 
exchanger coil from freezing is to use an inhibited ethylene 
or propylene glycol anti-freeze.  If this is not possible, an 
auxiliary heat load and minimum flow rate must be maintained 
on the coil at all times so that the water temperature does not 
drop below 10°C when the cooler is shut down. See 

Table 5

 

for recommended minimum flow rates.

If an anti-freeze solution is not used, the coil must be drained 
immediately whenever the pumps are shut down or flow stops.  
This is accomplished by having automatic drain valves and air 
vents in the piping to and from the cooler.  Care must be taken 
to ensure that the piping is adequately insulated and sized 

to allow the water to flow quickly from the coil.  This method 
of protection should be used only in emergency situations 
and is neither a practical nor recommended method of freeze 
protection.  Coils should not be drained for an extended 
period of time, as internal corrosion may occur.

When the unit is in operation during freezing weather, some 
type of capacity control is normally required in order to keep 
water temperatures from dropping below 10°C.  Operating 
dry with a remote sump is an excellent way of reducing unit 
capacity at low temperatures.  Other methods of capacity 
control include two-speed motors, VFDs and fan cycling. 
These can be used individually or in combination with dry/
remote sump operation.

Table 5

 - Closed Circuit Cooler Minimum Recommended Flow Rate

** Not available as eco-ATWE

Closed Circuit Cooler

Footprint

Minimum Flows

Standard 

Flow

GPM

Series Flow

GPM

Standard 

Flow

l/s

Series Flow

l/s

ATWB Products, eco-ATW & eco-ATWE

3’x3’**

4’ wide units**

7’ wide units

8.5’x7.5’

8.5’x9’ to 8.5’x21’

17’x12’, 17’x14

10’x12’, 10’x18’

10’x24, 10’x36’, 20’x12’, 20’x18’

20’x24’, 20’x36’

12’x12’, 12’x14’, 12’x18’, 12’x20’
12’x24’, 12’x28’, 12’x36’, 12’x40’
24’x12’, 24’x14’, 24’x18’, 24’x20’

24’x24’, 24’x28’, 24’x36, 24’x40’

74

140
148
160
320
188
376
752
232
464
464
928

26
37
70
74
80

160

94

188
376
116
232
232
464

4.7
8.8
9.3

10
20

11.9
23.7
47.4
14.6
29.3

11

58.5

1.6
2.3
4.4
4.7

5

10

5.9

11.9
23.7

7.3

14.6

11

29.3

LRWB Products

3’ wide units
5’ wide units
8’ wide units

60
94

148

30
47
74

3.8
5.9
9.3

1.9

3

4.7

LSWE Products

4’x6’, 4’x9’, 4’x12’, 4’x18’

5.5’x12’, 5.5’x18’

8’x12’, 8’x18’
8’x24’, 8’x36’

10’x12’, 10’x18’

10’x24, 10’x36’

66
94

148
296
188
376

30
47
74

148

94

188

66
94

148
296
188
376

30
47
74

148

94

188

ESW4 Products

8.5’x6’-LP

8.5’x9’, 8.5’x12’, 12’x12’-LP, 12’x12’-SP

8.5’x18’, 12’x12’-LF, 12’x12’-SF, 12’x18’-LF, 12’x18’X-SF

12’x18’X-LP, 12’x18’X-SP

12’x18’X-LF, 12’x18’X-SF

14’x22’

100
160
240
320
480
440

50
80

120
160
240
220

6.3

10.1
15.1
20.2
30.3
27.8

3.2

5

7.6

10.1
15.1
13.9

Содержание ATC-E

Страница 1: ...Box 1300 Westminster Maryland 21158 USA Phone 410 756 2600 Fax 410 756 6450 EVAPCO Europe bvba Heersterveldweg 19 Industrieterrein Oost 3700 Tongeren Belgium Phone 32 12 395029 Fax 32 12 238527 evapc...

Страница 2: ...A lock out tag out procedure integrated with the Process Control System must be foreseen by the customer A lockable disconnect switch should be located within sight of the unit for each fan motor ass...

Страница 3: ...could potentially cause damage to plastic components Label on the coil section s WARNING Do not operate the pressure vessel at service conditions outside of the PED nameplate located at the coil conne...

Страница 4: ...d minimum speeds and for recommendations on locking out resonance frequencies 5 Verify that a water treatment plan has been implemented including passivation of galvanized steel units See Water Treatm...

Страница 5: ...e fully opened before the pumps turn on If the system temperature continues to rise the unit fan is cycled on For a variable speed controller the fans are turned on to minimum speed See the Fan System...

Страница 6: ...38 C Regal R O 220 DTE Oil BB Teresstic 220 All bearings used on EVAPCO equipment are factory adjusted and self aligning Do not disturb bearing alignment by tightening the sleeve bearing caps Fan Bel...

Страница 7: ...if operating below 25 is possible NOTE Pump Motors VFD s should not be used on pump motors The pumps are designed to be operated at full speed and are not intended to be used as capacity control The t...

Страница 8: ...to minimum speed Should vibration inducing frequencies exist the run up and run down test will isolate the resonant frequencies which then must then be locked out in the VFD programming Two Speed Moto...

Страница 9: ...e is a bronze valve connected to a float arm assembly and is activated by a large foam filled plastic float The float is mounted on an all thread rod held in place by wing nuts The water level in the...

Страница 10: ...p When Supplied The pump and pump motor should be lubricated and serviced in accordance with the pump manufacturer s instructions The recirculation pump should not be used as a means of capacity contr...

Страница 11: ...f operation During this passivation period recirculating water pH should be maintained above 7 0 and below 8 0 at all times Since elevated temperatures have a harmful effect on the passivation process...

Страница 12: ...oling equipment can be considered as long as the resultant recirculating water chemistry conforms to the parameters noted in Table 3 It should be noted that using water reclaimed from other processes...

Страница 13: ...10 x24 20 x12 10 x18 10 x36 20 x18 12 x12 12 x14 12 x18 12 x24 12x28 12 x36 24 x12 24 x14 24 x18 24 x24 24 x28 24 x36 12 x20 12 x40 24 x20 24 x40 2 0 2 0 2 0 2 0 3 0 4 0 2 5 2 5 3 7 5 7 3 5 2 5 3 0 2...

Страница 14: ...ith a remote sump is an excellent way of reducing unit capacity at low temperatures Other methods of capacity control include two speed motors VFDs and fan cycling These can be used individually or in...

Страница 15: ...ser during the winter is to run the unit DRY In dry operation the recirculation pump is turned off the basin drained and air passes over the coil Instead of using evaporative cooling to cool the proce...

Страница 16: ...ethod of managing the amount of ice buildup is by cycling the fan motors off while keeping the pump on During these periods of idle fan operation the warm water that is absorbing the building load flo...

Страница 17: ...crape and coat with ZRC annually 10 Lubricate fan shaft bearings every 1000 hours of opera tion or every three months 11 Lubricate fan motor bearings see mfg s instructions Typi cally for non sealed b...

Страница 18: ...robe ends of scale build up quarterly 12 Electronic Water Level Controller Clean inside the standpipe annually 13 Solenoid Make up Valve Inspect and clean valve of debris as needed 14 Vibration Switch...

Страница 19: ...ned at least once a month by hand This can be accomplished by making sure the unit s disconnect is tagged and locked out and grasping the fan assembly rotating it several turns 9 Energize fan motor sp...

Страница 20: ...2013 EVAPCO Europe Bulletin 116R E Metric 0322 Operation and Maintenance Instructions...