background image

11

Operation and Maintenance Instructions

Water Treatment and Water Chemistry

Proper water treatment is an essential part of the maintenance 
required for evaporative cooling equipment.  A well designed 
and consistently implemented water treatment program will 
help to ensure efficient system operation while maximizing the 
equipment’s service life.  A qualified water treatment company 
should design a site specific water treatment protocol based 
on equipment (including all metallurgies in the cooling system), 
location, makeup water quality, and usage. 

Bleed or Blowdown

Evaporative cooling equipment rejects heat by evaporating a 
portion of the recirculated water into the atmosphere as warm, 
saturated discharge air.  As the pure water evaporates it leaves 
behind the impurities found in the system’s makeup water and 
any accumulated airborne contaminants.  These impurities 
and contaminants, which continue to recirculate in the system, 
must be controlled to avoid excessive concentration which 
can lead to corrosion, scale, or biological fouling.

Evaporative cooling equipment requires a bleed or blowdown 
line, located on the discharge side of the recirculating pump, 
to remove concentrated (cycled up) water from the system.  
EVAPCO recommends an automated conductivity controller 
to maximize the water efficiency of your system.  Based on 
recommendations from the water treatment company, the 
conductivity controller should open and close a motorized 
ball or solenoid valve to maintain the conductivity of the 
recirculating water.  If a manual valve is used to control the 
bleed rate, it should be set to maintain the conductivity of the 
recirculating water during periods of peak load at the maximum 
level recommended by the water treatment company.

Galvanized Steel – Passivation

‘White Rust’ is a premature failure of the protective zinc layer 
on hot dip or mill galvanized steel which can occur as a result 
of improper water treatment control during the start-up of 
new galvanized equipment.  The initial commissioning and 

passivation period is a critical time for maximizing the service 
life of galvanized equipment.  EVAPCO recommends that the 
site specific water treatment protocol includes a passivation 
procedure which details water chemistry, any necessary 
chemical addition, and visual inspections during the first six 
(6) to twelve (12) weeks of operation.  During this passivation 
period, recirculating water pH should be maintained above 
7.0 and below 8.0 at all times.  Since elevated temperatures 
have a harmful effect on the passivation process, the new 
galvanized equipment should be run without load for as much 
of the passivation period as is practical.

The following water chemistry promotes the formation of white 
rust and should be avoided during the passivation period:

 

1.  pH values in the recirculating water greater than 8.3.

 

2.  Calcium hardness (as CaCO

3

) less than 50 ppm in the 

recirculating water.

 

3.  Anions of chlorides or sulfates greater than 250 ppm 

in the recirculating water.

 

4.  Alkalinity greater than 300 ppm in the recirculating 

water regardless of pH value.

Changes in water chemistry control may be considered after 
the passivation process is complete as evidenced by the 
galvanized surfaces taking on a dull gray color.  Any changes 
to the treatment program or control limits should be made 
slowly, in stages while documenting the impact of the changes 
on the passivated zinc surfaces.  

  •  Operating galvanized evaporative cooling equipment 

with a water pH below 6.0 for any period may cause 
removal of the protective zinc coating.

  •  Operating galvanized evaporative cooling equipment 

with a water pH above 9.0 for any period may destabilize 
the passivated surface and create white rust.

  •  Re-passivation may be required at any time in the 

service life of the equipment if an upset condition occurs 
which destabilizes the passivated zinc surface. 

Water Chemistry Parameters

The water treatment program designed for evaporative cooling 
equipment must be compatible with the unit’s materials of 
construction, as well as other equipment and piping used 

in the system.  Control of corrosion and scale will be very 
difficult if the recirculating water chemistry is not consistently 
maintained within the ranges noted in 

Table 3

 

Property 

Z-725  

Type 304  

Type 316 

   

Galvanized Steel 

Stainless Steel 

Stainless Steel

  pH 

7.0 – 8.8 

6.0 – 9.5 

6.0 – 9.5

  pH During Passivation 

7.0 – 8.0 

N/A 

N/A

  Total Suspended Solids (ppm)* 

<25 

<25 

<25

  Conductivity (Micro-Siemens/cm) **  <2,400 

<4,000 

<5,000

  Alkalinity as CaCO

3

 (ppm) 

75 - 400 

<600 

<600

  Calcium Hardness CaCO

3

 (ppm) 

50 - 500 

<600 

<600

  Chlorides as Cl-(ppm) *** 

<300 

<500 

<2,000

  Silica (ppm) 

<150 

<150 

<150

  Total Bacteria (cfu/ml) 

<10,000 

<10,000 

<10,000

*   Based on standard EVAPAK

®

 fill

**   Based on clean metal surfaces.  Accumulations of dirt, deposits, or sludge will increase corrosion potential
***   Based on maximum coil fluid temperatures below 49°C

Table 3

 - Recommended Water Chemistry Guidelines

Содержание ATC-E

Страница 1: ...Box 1300 Westminster Maryland 21158 USA Phone 410 756 2600 Fax 410 756 6450 EVAPCO Europe bvba Heersterveldweg 19 Industrieterrein Oost 3700 Tongeren Belgium Phone 32 12 395029 Fax 32 12 238527 evapc...

Страница 2: ...A lock out tag out procedure integrated with the Process Control System must be foreseen by the customer A lockable disconnect switch should be located within sight of the unit for each fan motor ass...

Страница 3: ...could potentially cause damage to plastic components Label on the coil section s WARNING Do not operate the pressure vessel at service conditions outside of the PED nameplate located at the coil conne...

Страница 4: ...d minimum speeds and for recommendations on locking out resonance frequencies 5 Verify that a water treatment plan has been implemented including passivation of galvanized steel units See Water Treatm...

Страница 5: ...e fully opened before the pumps turn on If the system temperature continues to rise the unit fan is cycled on For a variable speed controller the fans are turned on to minimum speed See the Fan System...

Страница 6: ...38 C Regal R O 220 DTE Oil BB Teresstic 220 All bearings used on EVAPCO equipment are factory adjusted and self aligning Do not disturb bearing alignment by tightening the sleeve bearing caps Fan Bel...

Страница 7: ...if operating below 25 is possible NOTE Pump Motors VFD s should not be used on pump motors The pumps are designed to be operated at full speed and are not intended to be used as capacity control The t...

Страница 8: ...to minimum speed Should vibration inducing frequencies exist the run up and run down test will isolate the resonant frequencies which then must then be locked out in the VFD programming Two Speed Moto...

Страница 9: ...e is a bronze valve connected to a float arm assembly and is activated by a large foam filled plastic float The float is mounted on an all thread rod held in place by wing nuts The water level in the...

Страница 10: ...p When Supplied The pump and pump motor should be lubricated and serviced in accordance with the pump manufacturer s instructions The recirculation pump should not be used as a means of capacity contr...

Страница 11: ...f operation During this passivation period recirculating water pH should be maintained above 7 0 and below 8 0 at all times Since elevated temperatures have a harmful effect on the passivation process...

Страница 12: ...oling equipment can be considered as long as the resultant recirculating water chemistry conforms to the parameters noted in Table 3 It should be noted that using water reclaimed from other processes...

Страница 13: ...10 x24 20 x12 10 x18 10 x36 20 x18 12 x12 12 x14 12 x18 12 x24 12x28 12 x36 24 x12 24 x14 24 x18 24 x24 24 x28 24 x36 12 x20 12 x40 24 x20 24 x40 2 0 2 0 2 0 2 0 3 0 4 0 2 5 2 5 3 7 5 7 3 5 2 5 3 0 2...

Страница 14: ...ith a remote sump is an excellent way of reducing unit capacity at low temperatures Other methods of capacity control include two speed motors VFDs and fan cycling These can be used individually or in...

Страница 15: ...ser during the winter is to run the unit DRY In dry operation the recirculation pump is turned off the basin drained and air passes over the coil Instead of using evaporative cooling to cool the proce...

Страница 16: ...ethod of managing the amount of ice buildup is by cycling the fan motors off while keeping the pump on During these periods of idle fan operation the warm water that is absorbing the building load flo...

Страница 17: ...crape and coat with ZRC annually 10 Lubricate fan shaft bearings every 1000 hours of opera tion or every three months 11 Lubricate fan motor bearings see mfg s instructions Typi cally for non sealed b...

Страница 18: ...robe ends of scale build up quarterly 12 Electronic Water Level Controller Clean inside the standpipe annually 13 Solenoid Make up Valve Inspect and clean valve of debris as needed 14 Vibration Switch...

Страница 19: ...ned at least once a month by hand This can be accomplished by making sure the unit s disconnect is tagged and locked out and grasping the fan assembly rotating it several turns 9 Energize fan motor sp...

Страница 20: ...2013 EVAPCO Europe Bulletin 116R E Metric 0322 Operation and Maintenance Instructions...

Отзывы: