INSTALLATION INSTRUCTIONS
Examples of hydraulic installation: Top, side, rear.
Use of ½ inch pipes is recommended.
STORAGE WATER HEATER
MODE INSTALLATION
Remove the 2 covers for the installation of the system pipes and the fume
duct. The fume duct must be certified according to EN1856-2. The use of
flexible tubing is recommended to connect the appliance to the hydraulic
system as, in the case of routine or non-routine maintenance, this will make
it easier to move.
Hot and cold water pipes are ½ inch. The hot water pipe is indicated using a
sun and the cold water pipe is indicated with snowflake symbol.
IMPORTANT:
A circuit board and safety thermostat installed
in the item may reduce the risk of malfunction. Installation of
a safety hydraulic circuit according to EN 1487 is also
mandatory. It is a good practice to connect the drain of the
unit to a pipe with the required specifications.
Installation of an expansion tank is recommended to prevent
harmful water hammer or accidental overpressures from
occurring. A mixing valve to prevent water at
overtemperatures in the circuit must also be installed.
The manufacturer assume no liability for damage to property
or injury to persons following failure to install the safety
devices correctly.
THERMO-STOVE
MODE INSTALLATION
Remove the 2 covers for the installation of the system pipes and the fume
duct. The fume duct must be certified according to EN1856-2. The use of
flexible tubing is recommended to connect the appliance to the hydraulic
system as, in the case of routine or non-routine maintenance, this will make
it easier to move.
Delivery and return pipes are ½ inch. The delivery is indicated with a sun and
the return is indicated with the snowflake symbol.
Install the electronic pump and expansion tank according to the system and
as described above. The safety valve must be at a maximum of 4 BAR.
It is also recommended to install a dirt separator as the electronic pump could
capture the dirt of the system and become jammed. It is
RECOMMENDED
that an anti-condensation valve and a pressure gauge to read pressure are
installed. Remember to purge the hydraulic system before switching on the
appliance.
The system pressure must range from 0.5 to 2.5 bar. The recommended
pressure is 1.5 bar.
The manufacturer assume no liability for damage to property
or injury to persons following failure to install the safety
devices correctly.
14