7300A User Manual
6-9
Digital Communication
General Status Word (GSW) :
This parameter indicates the status of the main alarms from 1 to 7 and the status of moni-
toring during the time between communication frames. The byte containing 0 to 7 may be
read by Modbus function 7 (Quick Read). Bit definition :
Bit Definition
number
0
State ‘1’ : GRF alarm (TLF and THSC) active
1
State ‘1’ : PLF or TLF fault channel 1 (7100, 7200 and 7300)
2
State ‘1’ : PLF or TLF fault channel 2 (7200 and 7300 only)
3
State ‘1’ : PLF or TLF fault channel 2 (7200 and 7300 only)
4
Reserved
5
State ‘1’ : Power unit conduction stopped due to an alarm
6
State ‘1’ : Over-temperature alarm activated (fan-cooled unit)
7
State ‘1’ : Link failure with the communication option
for S basic versions with DLF and A versions
8
State ‘1’ : Time-out exceeded
9 à 15
Not used
Manufacturer Identifier (MI) :
This parameter returns ‘EUROTHERM Automation’ as an ASCII character string
(32 consecutive bytes read, starting at address 65280)
Command Word (CW) :
This parameter is used to modify the operation of the digital communication.
Codes and associated functions are given in the following table :
Command
Function
0
Inhibit firing
1
Enable firing
2
Enable supply variation compensation
3
Disable supply variation compensation
4
Modify reference for compensation
5
Transfer waiting setpoint to active setpoint
6
Alarms Acknowledgement
7
PLF rating demand
8
PLF monitoring disabled
The operations coded 2,3,4,7 and 8 are stored in permanent memory