7300A User Manual
1-5
Identification
1.2. TECHNICAL SPECIFICATIONS
1.2.1. Use
Thyristor unit, variant 4 (see Standard EN 60947-4-3)
for uninterrupted service.
1.2.2. Power
Nominal current per phase
16 A to 160 A at 45°C (see product code)
Nominal line to line voltage
200 V to 500 V (see code).
Frequency
Use from 47 to 63 Hz (automatic matching)
Dissipated power
1.3 W (approx.) per amp and per phase
Cooling
ratings
≤
100 A: Natural convection
ratings
≥
125 A: Fan-cooled.
1.2.3. Load
Three-phase Industrial Load.
Categories of use
The categories of use applicable for each unit are indicated
on the identification label
• AC-51 Non-inductive or low inductance loads, furnace
resistances
(Resistive load with low temperature coefficient).
• AC-55b Switching of incandescent lamps, for units
≤
100 A
(Short wave infrared elements, SWIR).
• AC-56a Switching of transformers
(Transformer primaries and high temperature
coefficient resistive loads).
Options must be fitted to 7300A units in order to comply
with certain categories of use.
Connections
Independent of phase rotation order
Load configuration
Star with or without neutral, open or closed delta.
Configuration on order.
1.2.4. Signalling
Electronics supply present (green ‘ON’ LED) and supply
fault detection (‘ON’ LED flashing).
Thyristor firing request : (green ‘HEAT’ LED).
1.2.5. Dimensions
Rating
Height
Width
Depth (mm)
Base One Option Option +
only or Comms
Comms only
16 A à 40 A 220 mm 96 mm 164 189
239
63 A à 100 A 305 mm 144 mm 295 295
372
125 A à 160 A 498 mm 144 mm 295 295
372