7300A user Manual
2-7
Installation
2.4. POWER CONNECTIONS
Rating
Terminal capacity
Torque
Stripping length
A
mm
2
AWG
Nm
mm
16 to 25
2.5 to
6
13 to 9
1.2
13
40 to 63
6
to 16
9
to 5
1.8
13
80 to 100
16 to 35 5 to 2
3.8
20
16,4 (or 28,8)
125 50
to 120
0
M10 nut
ø 10 (or ø 12)
160 70
to 120
00
to attach eyelet
and terminal
2.4.1. General (Ratings from 16 A to 160 A)
7300A power thyristor units comprise three channels controlled by thyristors.
Terminals 1/L1, 3/L2 and 5/L3 must be wired to the three-phase supply network.
Terminals 2/T1, 4/T2 and 6/T3 must be wired to the three-phase load.
The protective earth terminal PE (marked with the earth symbol) must be wired to the
protective earth (see section ‘Safety during installation’).
Table 2-2 Power connection details for ratings from 16 A to 160 A
Conductor cross-sections should comply with IEC 60943.
Use at 75°C min.copper wire only
2.4.3. Three-phase load wiring schemes
Power connections to the thyristor unit depend on the load configuration scheme.
The following four configuration schemes may be used for three-phase loads:
• star without neutral (3 connection wires, code 3S), figure 2-7
• star with neutral (4 connection wires, code 4S), figure 2-8
• closed delta (3 connection wires, code 3D), figure 2-9
• open delta (6 connection wires, code 6D), figure 2-10
2.4.2. Power connection details