Control / Limits
7300A User Manual
4-6
NOTE:
I
2
current Control and Limitation operating condifiotns :
1 - Standard
If the gap between of the three currents squared is less than 25% of the calibrated nominal
current I
N
2
, then the control is achived at the mean value of the three currents squared.
∆
I
i
2
< 25% I
N
2
then I
2
= (I1
2
+I2
2
+I3
2
)/3
i = 1,2,3
2 - In the case of an unbalanced load.
If the gap is more than 25%, then the control is achieved at the squared value of
the highest current value.
∆
I
i
2
> 25% I
N
2
then I
2
= Imax
2
i = 1,2,3