Programming Your Application
6-53
590+ Series DC Digital Converter
Functional Description
RAMP INPUT
MIN. SPEED
Jog /
I/P
O/P
1
0
RAMP DECEL TIME
RAMP ACCEL TIME
RAMP HOLD
AUTO RESET
EXTERNAL RESET
RESET VALUE
Slack
"S" RAMP
0
I/P
O/P
t
% S-RAMP
RAMPING THRESH.
RAMPING
RAMP OUTPUT
EXTERNAL RESET
Range: See below
If TRUE, then the ramp is held in reset. EXTERNAL RESET does not depend on AUTO
RESET for its operation.
0 : DISABLED
1 : ENABLED
RESET VALUE
Range: -300.00 to 300.00 %
This value is pre-loaded into the output when RAMP RESET is TRUE, or at power-up. In
order to catch a spinning load smoothly (`bumpless transfer’) connect SPEED FEEDBACK
Tag No. 62 (source) to RESET VALUE Tag No. 422 (destination).
MIN. SPEED
Range: 0.00 to 100.00 %
(MIN SPEED)
The minimum speed clamp is fully bi-directional and operates with a 0.5% hysterisis. This
clamp operates on the input to the ramp and it can therefore be overridden by the RESET
VALUE as far as the ramp output is concerned.
Input
Output
Minimum Speed
-0.5
0
0.5
Содержание 590+ Series
Страница 16: ...1 4 Getting Started 590 Series DC Digital Converter ...
Страница 58: ...3 32 Installing the Converter 590 Series DC Digital Converter Figure 3 11 Frame 2 40A 165A Stack Assembly ...
Страница 76: ...3 50 Installing the Converter 590 Series DC Digital Converter ...
Страница 110: ...5 14 The Operator Station 590 Series DC Digital Converter ...
Страница 194: ...7 10 Trips and Fault Finding 590 Series DC Digital Converter ...
Страница 208: ...9 6 Control Loops 590 Series DC Digital Converter ...
Страница 236: ...10 28 Parameter Specification Table 590 Series DC Digital Converter ...
Страница 260: ...11 24 Technical Specifications 590 Series DC Digital Converter ...
Страница 274: ...12 14 Certification for the Converter 590 Series DC Digital Converter ...
Страница 300: ...15 2 The Default Application 590 Series DC Digital Converter ...
Страница 308: ......