EUROSTER 11K CONTROLLER USER MANUAL
9
If the modified setting depends on another more important (key) parameter, the
system will prevent any incorrect modification. For example, the throttle activation
temperature may not be set higher than the alarm temperature.
6. SYSTEM LAYOUTS
Use the
SC
service parameter to select the actual system layout. The below shown diagrams
are simplified, not all elements necessary for correct operation of the system are shown.
Legend:
S1, S2
1
st
/2
nd
temperature sensor
RT
room thermostat
P1, P2, P3
1
st
/2
nd
/3
rd
pump
THROTTLE
combustion air throttle
a) Layout 1: CH system with plate heat exchanger
P1
pump is activated if the fireplace temperature exceeds the preset temperature
P2
pump is activated with a delay in respect to P1 activation time if the fireplace
temperature exceeds the preset temperature
P3
alarm output is activated if the fireplace temperature exceeds the critical
temperature
AUX
output is deactivated if the fireplace temperature exceeds the
AUX
temperature or
RT
is turned off
Throttle is controlled (open/closed) to maintain the preset temperature.
b) Layout 2: CH system with heat buffer
P1
pump is activated if the fireplace temperature exceeds the preset temperature and
is sufficiently higher than the heat buffer temperature
P2
pump is activated if the buffer temperature exceeds the preset temperature and the
RT
signal is ON
P3
alarm output is activated if the fireplace temperature exceeds the critical
temperature
AUX
output is deactivated if the heat buffer temperature exceeds the
AUX
temperature
or
RT
is turned off
Throttle is controlled (open/closed) to maintain the preset temperature.