2123041-08-01/21 (translation of the original operating instructions)
Operating Instructions
Transponder-Coded Safety Switch CTP-AR
EN
10.9. Connection of a single CTP-AR
If a single CTP-AR is used, connect the switch as shown in
. The monitoring outputs can be routed to a control system.
The switches can be reset via the RST input. To do this, a voltage of 24 V is applied to the RST input for at least 3 s. The
RST input must be connected to 0 V if it is not used.
WARNING
In the event of a fault, loss of the safety function due to incorrect connection.
Ì
To ensure safety, both safety outputs (FO1A and FO1B) must always be evaluated.
Important!
Ì
The example shows only an excerpt that is relevant for connection of the CTP system. The exam-
ple illustrated here does not show complete system planning. The user is responsible for safe inte-
gration into the overall system. Detailed application examples can be found at www.euchner.com.
Simply enter the order number of your switch in the search box. You will find all available connec-
tion examples for the device in
Downloads
.
Safety outputs
Door monitoring
Safety inputs
Read head
Actuato
r
Monitoring outputs
X2:5
NC
X2:3
OI
Diagnostics
Guardlocking
active
FI1A
X1:6
FI1B
X1:1
-B1
UB
X1:2
IMP
X2:4
X2:1
IMM
RST
X1:8
X1:7
0V UB
X2:2
OD
X1:3
FO1A
X1:4
FO1B
X1:5
OL
CTP
24V DC
0V
Connected load
1
2
-F1
1
2
-F2
0V
/
24V
/
Figure 4:
Connection example for separate operation, version with plug connectors 2xM12