Operating Instructions
Transponder-Coded Safety Switch CTP-AR
18
(translation of the original operating instructions) 2123041-08-01/21
10.4. Requirements for connecting cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connecting cables.
Ì
Use connection components and connecting cables from EUCHNER.
Ì
On the use of other connection components, the requirements in the following table apply.
EUCHNER provides no warranty for safe function in case of failure to comply with these require-
ments.
Observe the following requirements with respect to the connecting cables:
For safety switch CTP-…-AR-…-SAB-… with plug connectors 2 x M12
Parameter
Value
Unit
Conductor cross-section, min.
0.25
mm²
R max.
60
W
/km
C max.
120
nF/km
L max.
0.65
mH/km
Recommended cable type
LIYY 8 x 0.25 mm² or 5 x 0.34 mm²
For safety switch CTP-…-AR-…-SH-… with plug connector M23 (RC18)
Parameter
Value
Unit
Conductor cross-section, min.
0.25
mm²
R max.
60
W
/km
C max.
120
nF/km
L max.
0.65
mH/km
Recommended cable type
LIFY11Y min. 19-core