17
2121341-06-11/20 (Translation of the original operating instructions)
Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
EN
5.6. Module PROFIBUS CE-PR
DB9 female plug
(view on front)
PIN
SIGNAL
DESCRIPTION
1
-
2
-
3
B-line
Positive RS485 RxD/TxD
4
RTS
Request to send
5
GND bus
0 VDC (isolated)
6
5V
+5 VDC (insulated/short circuit-proof)
7
-
-
8
A-line
Negative RS485 RxD/TxD
9
-
-
Housing
Shielding
Connected internally to protective earth
(acc. to PROFIBUS standard)
MODE LED
STATUS
INDICATION
DESCRIPTION
GREEN
On-line
Data exchange
GREEN flashing
On-line
AVAILABLE
RED flashing
(1 flash)
Parameterization error
See IEC 61158-6
RED flashing
(2 flashes)
PROFIBUS
configuration error
Configuration data for MASTER or CE-PR
incorrect
STS LED
STATUS
INDICATION
DESCRIPTION
OFF
CE-PR not initialized
SETUP STATE or NW_INIT
GREEN
Initialized
End of initialization NW_INIT
GREEN flashing
Initialized with diagnostic
active
EXTENDED DIAGNOSTIC bit set
RED
Exception error
EXCEPTION STATE
5.7. Module EtherCAT (CE-EC)
STS LED
STATUS
INDICATION
DESCRIPTION
OFF
INIT
INITIALIZATION or no voltage
GREEN
OPERATIONAL
OPERATIONAL status
GREEN flashing
PRE-OPERATIONAL
PRE-OPERATIONAL status
GREEN one flash
SAFE-OPERATIONAL
SAFE-OPERATIONAL status
RED
(Fatal Event)
System inhibited
ERR LED
STATUS
INDICATION
DESCRIPTION
OFF
No error
No error or no voltage
RED flashing
Configuration not valid
Status change requested by master not
possible
RED one flash
Unsolicited state change
Use of the slave changed the module
status
RED two flashes
Watchdog timeout
Watchdog timeout in the Sync Manager
RED
Controller fault
Bus module in EXCEPTION state