19
2121341-06-11/20 (Translation of the original operating instructions)
Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
EN
5.10. Module PROFINET CE-PN
NET LED
STATUS
INDICATION
DESCRIPTION
OFF
Offline
No voltage
No connection to I/O control system
GREEN
Online (Run)
Connection to
I/O control system established
I/O control system RUN state
GREEN one flash
Online (Stop)
Connection to
I/O control system established
I/O control system STOP state
GREEN flashing
Blink
Identification of the network node
RED
Fatal event
Severe internal error
(in combination with RED STS)
RED one flash
Station name error
Station name not configured
RED two flashes
IP address error
IP address not configured
RED three flashes
Configuration error
Error during identification
STS LED
STATUS
INDICATION
DESCRIPTION
OFF
Not initialized
-
GREEN
Normal operation
-
GREEN one flash
Diagnostic event
-
RED
Exception /Fatal event
Module in the EXCEPTION/
severe internal error state
(in combination with RED NET)
5.11. Module Modbus TCP/IP CE-MT
NET LED
STATUS
INDICATION/ DESCRIPTION
OFF
No voltage or no IP address
GREEN
Module in the active process or on standby
GREEN flashing
Waiting for connection
RED
Duplicate IP address or unrecoverable error
RED flashing
Timeout for active process
STS LED
STATUS
INDICATION
DESCRIPTION
OFF
No power
-
Green
RUN state
Normal operation
RED
Fatal error
Ì
Serious error;
Ì
module in the EXCEPTION state (or
serious exception error)
RED flashing
Error
Ì
Minor errors in the diagnostic object
Ì
IP conflict