RDM-31-0322
NORD
canopy
|
OZ 3.1 Installation Guide
5.2 Control Panel and the Ozone Modules data wiring
Three cables are connected to the Control Panel. Data cable (3x0,25mm2) for communication between Control
Panel and EOZ unit, I/O cable (5x0,5mm2) for connecting to the building automation and LAN cable to access
the Control Panel via internet.
Ozone Modules are connected sequentially (”daisy-chained”) from the Control Panel to the nearest Ozone
Module, then to the next module and so on. However, please note that although the physical cabling is
”chained” from one device to the next, the data cables are connected together in a parallel format. That is,
similar terminals between devices are connected together; there are no specific ”in” or ”out” data terminals
on the various components.
Maximum limit for the number of Ozone Module connected to the Control Panel is 99 and maximum length of
the data cable is 500m. However, it may be advantageous to have multiple Control Panels in larger facilities.
Cable bushings come preattached inside the supply chambers.
*
3x0,25 mm2 or another shielded data cable with at least 3 conductors.
Data terminal A-, B+ and C (GND) are connected similarly between the Control Panel and each Ozone Module.
Note the cable colors used on each terminal to ensure all devices are connected similarly.
Display
Ozone Module 1
PE
L
N
Junction box AP9
Circuit braker
10A fuse
(max 6 ozonators)
3x0,25 mm²
*
3x0,25 mm²
*
3x0,25 mm²
*
Ozone Module 2
Ozone Module ...
Display
Ozone Module 1
Ozone Module 2
Ozone Module ...
Control Panel
Data cable
A
B+
C